![Gree GC201808-III Скачать руководство пользователя страница 273](http://html.mh-extra.com/html/gree/gc201808-iii/gc201808-iii_service-manual_2260766273.webp)
GREE GMV5 HR HEAT RECOVERY UNITS
269
Troubleshooting:
2.2.4.122
“P5” Inverter compressor overcurrent protection
Error display:
ODU mainboard will display
Error judgment condition and method:
Check the error code on nixie tube of ODU main control board. If P5 is displayed, it indicates
inverter compressor overcurrent protection
Possible reason:
■Poor contact of compressor UVW wire;
■Connection sequence of compressor UVW wire is wrong;
■Compressor is broken;
■System is blocked;
■Compressor drive board IPM module is broken.