![Gree GC201808-III Скачать руководство пользователя страница 95](http://html.mh-extra.com/html/gree/gc201808-iii/gc201808-iii_service-manual_2260766095.webp)
GREE GMV5 HR HEAT RECOVERY UNITS
91
NOTICE!
①
If there are multiple modules for the modular ODU, the master unit must be the first ODU
module on the communication cable and cannot be connected to the IDU. (The master unit is
set by SA8 on the main board of the ODU.)
②
If there are multiple modules for the modular ODU, the IDU must be connected to the slave
module of the last ODU. (The slave unit is set by SA8 on the main board of the ODU.)
③
The communication cable and power cable must be laid separately to avoid interference.
④
The communication cable must be long enough to avoid joints.
⑤
Indoor units must be connected in series. The last IDU shall be connected to a matching
resistor (placed in the package of the ODU).
3.3.2 Communication cable connection between the IDU and wired
controller
Connection modes for the communication cable between the IDU and wired controller are shown in
the following figures.
One wired controller controlling one IDU
Two wired controllers controlling one IDU
One wired controller controlling multiple IDUs
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...