GREE GMV5 HR HEAT RECOVERY UNITS
16
Outdoor Units_Heat Recovery
Ton
18
20
22
Model
-
GMV-Q216WM/B-F(U)
GMV-Q240WM/B-F(U) GMV-Q264WM/B-F(U)
Module combination
-
GMV-Q96WM/B-F(U)
+GMV-Q120WM/B-F(U)
GMV-Q120WM/B-F(U)
+GMV-Q120WM/B-F(U)
GMV-Q72WM/B-F(U)
+GMV-Q96WM/B-F(U)
+GMV-Q96WM/B-F(U)
pressure
in.W.G
0.328
0.328
0.328
Ambient
temperature
range
Cooling
°C
-5~52
-5~52
-5~52
°F
23~125.6
23~125.6
23~125.6
Heating
°C
-20~24
-20~24
-20~24
°F
-4~75.2
-4~75.2
-4~75.2
Refrigerant
Refrigerant Type
-
R410A
R410A
R410A
Refrigerant Charge
Volume
kg
11.2+11.7
11.7+11.7
9.6+11.2+11.2
lbs.
24.69+25.79
25.79+25.79
21.16+24.69+24.69
Control
-
EXV
EXV
EXV
Pipe
Connection
Low pressure Gas
Pipe Size
mm
28.6
34.9
34.9
in.
1 1/8
1 3/8
1 3/8
high pressure gas
pipe
mm
28.6
28.6
28.6
in.
1 1/8
1 1/8
1 1/8
Liquid Pipe Size
mm
15.9
15.9
19.05
in.
5/8
5/8
3/4
Dimensions
(width×depth
×height)
External Dimension
mm
1340×765×1605
+1340×765×1605
1340×765×1605
+1340×765×1605
1340×765×1605
+1340×765×1605
+1340×765×1605
in.
52-3/4×30-1/8×63-1/5
+52-3/4×30-1/8×63-1/5
52-3/4×30-1/8×63-1/5
+52-3/4×30-1/8×63-1/5
52-3/4×30-1/8×63-1/5
+52-3/4×30-1/8×63-1/5
+52-3/4×30-1/8×63-1/5
Packaging
Dimension
mm
1420×840×1775
+1420×840×1775
1420×840×1775
+1420×840×1775
1420×840×1775
+1420×840×1775
+1420×840×1775
in.
55-7/8×33-1/8×69-7/8
+55-7/8×33-1/8×69-7/8
55-7/8×33-1/8×69-7/8
+55-7/8×33-1/8×69-7/8
55-7/8×33-1/8×69-7/8
+55-7/8×33-1/8×69-7/8
+55-7/8×33-1/8×69-7/8
Weight
Net Weight
kg
310+360
360+360
302+310+310
lbs.
683+794
794+794
666+683+683
Gross Weight
kg
325+375
375+375
317+325+325
lbs.
716+827
827+827
699+716+716
Maximum qty of connected indoor
units
unit
36
39
46
Protection
Devices
High Pressure
Protection
High pressure sensor, High pressure switch
Compressor /Fan
Over-current protection, Over-heat protection
Inverter
Over-current protection, Over-heat protection, High/Low voltage protection,
Remark
It refers to the operation power of compressor under ARI test conditions (Condensing temp. 130°F;
Evaporating temp.45°F; Return gas temp.65°F; Liquid temp.115°F) at 60Hz.
Oil charge includes the total oil amount of outdoor units, residual oil amount of compressor and oil
separate tank. When replacing the compressor or oil separate tank, only the corresponding required
oil amount shall be charged.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...