GREE GMV5 HR HEAT RECOVERY UNITS
82
d. Other places deemed as unreliable
(5) The power cable and the communication cable must be laid separately with a distance of
greater than 200mm (7.87inch). Otherwise, the communication of the unit will be affection.
Power cable and communication cable cannot come across and they should be at least 200mm
(7.87 inch) away from each other, otherwise, unit may work abnormally.
2.2 Requirements on Power Cable Configuration
Configure a circuit breaker to each unit for short circuit and overload protection. In addition,
configure a general circuit breaker to both the indoor and ODUs to switch on or switch off the general
power of the IDU or ODU.