GREE GMV5 HR HEAT RECOVERY UNITS
102
3 FUNCTION SETTINGS OF ODUS
Function application of ODUs consists of function DIP switch settings and function button settings,
including special engineering requirements.
3.1 System Function DIP Switch Settings
DIP Switch
Name
Meaning
Factory Settings
Remark
SA1
capacity
Capacity
DIP switch
Defines the rated
capacity of the unit.
Defined based on
the model.
The factory settings cannot be changed.
SA2
Addr-CC
Centralized
control
address DIP
switch
Defines and differentiates
addresses of different
systems in the case of
centralized control by
multiple systems.
00000
The address DIP switch is used only when
centralized control is required. Otherwise,
the factory settings are used without being
changed. The address DIP switch is valid
only when it is set on the master unit.
SA3
COMP-E
2#-6#
compressor
emergency
operation
DIP switch
Provides aftersales
emergency settings for
2#-6# compressors.
00000
It is better not to use the emergency
function. Replace the compressor at the
first time when an exception occurs.
SA4
I/M-E
1#
compressor/
module
emergency
operation
DIP switch
Provides aftersales
emergency settings for 1#
compressor/module.
00
It is better not to use the emergency
function. Replace the compressor at the
first time when an exception occurs.
SA5
FAN-E
Fan
emergency
operation
DIP switch
Provides aftersales
emergency settings for
fans.
00
It is better not to use the emergency
function. Replace relevant parts of the fan at
the first time when an exception occurs.
SA6
ESP_S
Outdoor
fan static
pressure
setting DIP
switch
Sets the static pressure of
the fan according to the
static pressure of the
exhaust pipeline
connected with the
engineering unit, to
guarantee normal
operation of the unit.
00
This DIP switch should be set based on
actual engineering conditions, neither
over-large nor over-small. It is
unnecessary to change the factory
settings in outdoor scenarios.
SA7
Reserved
DIP switch
——
00
——
SA8
MASTER-S
Master unit
setting DIP
switch
Defines the master unit.
00
A master unit must be set, and only one
master unit can be set in each
refrigerating system. This DIP switch is
mandatory. The default factory setting is
the master unit status.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...