GREE GMV5 HR HEAT RECOVERY UNITS
13
Outdoor Units_Heat Recovery
Ton
12
14
Model
-
GMV-Q144WM/B1-F(U)
GMV-Q168WM/B1-F(U)
Module combination
-
GMV-Q144WM/B1-F(U)
GMV-Q168WM/B1-F(U)
cfm
8240
9417
Max. external static pressure
Pa
82
82
in.W.G
0.328
0.328
Ambient
temperature
range
Cooling
°C
-5~52
-5~52
°F
23~125.6
23~125.6
Heating
°C
-20~24
-20~24
°F
-4~75.2
-4~75.2
Refrigerant
Refrigerant Type
-
R410A
R410A
Refrigerant Charge Volume
kg
11.7
11.7
lbs.
25.79
25.79
Control
-
EXV
EXV
Pipe Connection
Low pressure Gas Pipe Size
mm
28.60
28.60
in.
1 1/8
1 1/8
high pressure gas pipe Size
mm
22.20
22.20
in.
7/8
7/8
Liquid Pipe Size
mm
12.70
5.90
in.
1/2
5/8
Dimensions
(width×depth
×height)
External Dimension
mm
1340×765×1605
1340×765×1740
in.
52-3/4×30-1/8×63-1/5
52-3/4×30-1/8×68-1/2
Packaging Dimension
mm
1420×840×1775
1420×840×1910
in.
55-7/8×33-1/8×69-7/8
55-7/8×33-1/8×75 1/4
Weight
Net Weight
kg
370
395
lbs.
816
871
Gross Weight
kg
385
411
lbs.
849
906
Maximum qty of connected indoor units
unit
23
29
Protection
Devices
High Pressure Protection
High pressure sensor, High pressure switch
Compressor /Fan
Over-current protection, Over-heat protection
Inverter
Over-current protection, Over-heat protection, High/ Low voltage
protection,
Remark
Rating conditions:
Cooling: indoor 26.7°C(80°F) D.B./19.4°C(67°F)W.B; outdoor: 35°C(95°F)D.B.
Heating: indoor 21.1°C(70°F) D.B.; outdoor: 8.3°C(47°F)D.B./6.1°C(43°F)W.B.
It refers to the operation power of compressor under ARI test conditions (Condensing temp. 130°F,
Evaporating temp.45°F, Return gas temp.65°F. Liquid temp.115°F) at 60Hz.
Oil charge includes the total oil amount of outdoor units, residual oil amount of compressor and oil
separate tank. When replacing the compressor or oil separate tank, only the corresponding required oil
amount shall be charged.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...