Preaction Sprinkler DS21-24
für Nassanlagen
Maße in
mm
; Gewicht in
kg/St.
Preaction Sprinkler DS21-24
for wet pipe systems
dimensions in
mm; weight in kg/pc
technical data:
spray characteristics .....................spray sprinkler SP, pendent
response sensitivity .............................fast response RTI < 50
release temperature ...........................................................68 °C
operating pressure .....................................................min. 3 bar
sprinkler body ...........................................brass, chrome-plated
coverage area each Preaction Sprinkler .................max. 9 m²
K factor Preaction Sprinkler ....................................................57
note:
The VdS must agree to the application of Preaction
Sprinklers. (Not required in separated rooms of the fire
hazard class LH and OH with a maximum base area of
30 m²)
Techn. Daten:
Sprühcharakteristik ..................Schirmsprinkler SP, hängend
Ansprechempfindlichkeit ................Fast-Response RTI < 50
Auslösetemperatur ............................................................68 °C
Betriebsdruck ..............................................................min. 3 bar
Sprinklerkörper ...........................................Messing, verchromt
Schutzfläche je Preaction Sprinkler ..........................max. 9 m²
K-Wert Preaction Sprinkler .....................................................57
Hinweis:
Der Einbau der Preaction Sprinkler ist mit dem VdS abzu-
stimmen. (Nicht erforderlich in abgetrennten Räumen der
Brandgefahrenklasse LH und OH mit einer maximalen
Grundfläche von 30 m².)
Bezeichnung
designation
Art.-Nr.
order no.
Gewicht
weight
Preaction Sprinkler DS21 - 68 °C-24
84 4085
2,3
G4870031
*
*
*
U11-1"
U12-1"
oder
or