12.8 H: Terminal Function Selection
YASKAWA
SIEPC71061753A GA500 Technical Manual
627
4 : Digital Output Only
■
H2-36: Comparator 1 Ineffective Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-36
(159E)
Comparator 1 Ineffective
Time
Sets the length of time that
CP1 [Comparator1 Limit Fault]
is disabled.
0.0 s
(0.0 - 1000.0 s)
Note:
•
After you enter a Run command and wait for the time set in this parameter, the drive will monitor operation and make sure that it is in
the Comparator 1 range until you enter the Stop command.
•
When
CP1
detection is disabled, the drive will activate the output terminal set for
Comparator 1 [H2-xx = 66]
.
■
H2-37: Comparator 2 Ineffective Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-37
(159F)
Comparator 2 Ineffective
Time
Sets the length of time that
CP2 [Comparator2 Limit Fault]
is disabled.
0.0 s
(0.0 - 1000.0 s)
Note:
•
After you enter a Run command and wait for the time set in this parameter, the drive will monitor operation and make sure that it is in
the Comparator 2 range until you enter the Stop command.
•
When
CP2
detection is disabled, the drive will activate the output terminal set for
Comparator 2 [H2-xx = 67]
.
■
H2-40: Mbus Reg 15E0h bit0 Output Func
No.
(Hex.)
Name
Description
Default
(Range)
H2-40
(0B58)
Mbus Reg 15E0h bit0
Output Func
Sets the MFDO for bit 0 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
■
H2-41: Mbus Reg 15E0h bit1 Output Func
No.
(Hex.)
Name
Description
Default
(Range)
H2-41
(0B59)
Mbus Reg 15E0h bit1
Output Func
Sets the MFDO for bit 1 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
■
H2-42: Mbus Reg 15E0h bit2 Output Func
No.
(Hex.)
Name
Description
Default
(Range)
H2-42
(0B5A)
Mbus Reg 15E0h bit2
Output Func
Sets the MFDO for bit 2 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
■
H2-60: Term MA,MB,MC Secondary Function
No.
(Hex.)
Name
Description
Default
(Range)
H2-60
(1B46)
Expert
Term MA,MB,MC
Secondary Function
Sets the second function for terminal MA/MB-MC. Outputs the logical calculation results of the
terminals assigned to functions by
H2-01 [Term MA,MB,MC Function Selection]
.
F
(0 - FF)
■
H2-61: Term MA,MB,MC Logical Operation
No.
(Hex.)
Name
Description
Default
(Range)
H2-61
(1B47)
Expert
Term MA,MB,MC Logical
Operation
Sets the logical operation for the functions set in
H2-01 [Term MA,MB,MC Function Selection]
and
H2-60 [Term MA,MB,MC Secondary Function]
.
0
(0 - 8)
Note:
Refer to
Output of Logical Operation Results of MFDO on page 621
for more information about the relation between parameter settings
and logical operations.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...