190
YASKAWA
SIEPC71061753A GA500 Technical Manual
Drive Model
Maximum Applicable Motor Output
kW (HP)
Time Delay Fuse
Semiconductor Protection Fuse Rated Current
Manufacturer: EATON/Bussmann
ND
HD
Class J, CC, and T Fuse
Rated Current
A
Model
Input Rated Current
A
4038
18.5 (25)
15.0 (20)
-
FWH-175B
175
4044
22.0 (30)
18.5 (25)
-
FWH-200B
200
4060
30.0 (40)
22.0 (30)
-
FWH-200B
200
◆
Low Voltage Wiring for Control Circuit Terminals
You must provide low voltage wiring as specified by the National Electric Code (NEC), the Canadian Electric
Code, Part I (CEC), and local codes. Yaskawa recommends the NEC class 1 circuit conductor. Use the UL
approved class 2 power supply for external power supply.
Table 5.19 Control Circuit Terminal Power Supplies
Input/Output
Terminals
Power Supply Specifications
Digital input
S1 to S7, SN, SC, SP
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external
power supply.
Analog input
A1, A2, AC ,+V
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external
power supply.
Analog output
AM, AC
Uses the LVLC power supply in the drive.
Pulse train output
MP, AC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external
power supply.
Pulse Train Input
RP, AC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external
power supply.
Safe disable input
H1, H2, HC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external
power supply.
Serial communication input/output
D+, D-, AC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external
power supply.
24 V external power supply
PS, AC
Use the UL Listed class 2 power supply.
◆
Drive Motor Overload and Overheat Protection
The drive motor overload and overheat protection function complies with the National Electric Code (NEC) and
the Canadian Electric Code, Part I (CEC).
Set the Motor Rated Current and
L1-01 through L1-04 [Motor Overload Protection Select]
correctly to enable
motor overload and overheat protection.
Refer to the control method and set the motor rated current with
E2-01 [Motor Rated Current (FLA)]
,
E5-03 [PM
Motor Rated Current (FLA)]
, or
E9-06 [Motor Rated Current (FLA)]
.
■
E2-01: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E2-01
(030E)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by o2-04, C6-
01
(10% to 200% of the drive
rated current)
Note:
•
If
E2-01 < E2-03 [Motor No-Load Current]
, the drive will detect
oPE02 [Parameter Range Setting Error]
.
•
When the drive model changes, the display units for this parameter also change.
–
0.01 A: 2001 to 2042, B001 to B018, 4001 to 4023
–
0.1 A: 2056 to 2082, 4031 to 4060
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...