6.3 MEMOBUS/Modbus Communications
216
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
Reading the Contents of Non-Consecutive Holding Registers
The drive uses function code 67 (Hex.) and subfunction code 010D (Hex.) to read data with a maximum of 120
holding registers.
You must give the holding register number from which to read separately.
shows example messages when you read the frequency reference and torque limit from the drive for
slave 1.
uses this register data for the examples.
•
0024H:
U1-01 [Frequency Reference]
= 60.00 Hz (6000 = 1770H)
•
0028H:
U1-09 [Torque Reference]
= 100.0% (1000 = 03E8H)
Table 6.7 Message Example When Reading the Contents of Non-Consecutive Holding Registers
Byte
Command Message
Response Message (When Normal)
Response Message (When There is a Fault)
Setting Data
(Hex.)
Setting Data
(Hex.)
Setting Data
(Hex.)
0
Slave address
01
Slave address
01
Slave address
01
1
Function code
67
Function code
67
Function code
E7
2
Subfunction
code
Upper
01
Subfunction
code
Upper
01
Error code
02
3
Lower
0D
Lower
0D
CRC-16
Upper
EA
4
Data Quantity
Upper
00
Byte No.
Upper
00
Lower
31
5
Lower
02
Lower
04
-
6
Holding register
1 No.
Upper
00
Holding register
1 data
Upper
17
-
7
Lower
24
Lower
70
-
8
Holding register
2 No.
Upper
00
Holding register
2 data
Upper
03
-
9
Lower
28
Lower
E8
-
10
CRC-16
Upper
8B
CRC-16
Upper
47
-
11
Lower
29
Lower
ED
-
Note:
The number of bytes set in the command message set the data quantity × 2 during the command message.
■
Writing to Non-Consecutive Holding Registers
The drive uses function code 67 (Hex.) and subfunction code 010E (Hex.) to read data with a maximum of 60
holding registers.
You must give the holding register number from which to write separately.
shows example messages when you write the frequency reference and torque limit from the drive for
slave 1.
uses these specified holding registers data for the examples.
•
0002H: Frequency Reference = 60.00 Hz (6000 = 1770H)
•
0004H: Torque Limit = 150.0% (1500 = 05DCH)
When you rewrite the parameter value with the write command through the
H5-11 [Comm ENTER Command
Mode]
setting, you must use the Enter command to save and enable the contents of the changes. Refer to
Comm ENTER Command Mode on page 656
and
for more information.
Table 6.8 Message Example When Writing to Non-Consecutive Holding Registers
Byte
Command Message
Response Message (When Normal)
Response Message (When There is a Fault)
Setting Data
(Hex.)
Setting Data
(Hex.)
Setting Data
(Hex.)
0
Slave address
01
Slave address
01
Slave address
01
1
Function code
67
Function code
67
Function code
E7
2
Subfunction
code
Upper
01
Subfunction
code
Upper
01
Error code
02
3
Lower
0E
Lower
0E
CRC-16
Upper
EA
4
Data Quantity
Upper
00
Data Quantity
Upper
00
Lower
31
5
Lower
02
Lower
02
-
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...