YASKAWA
SIEPC71061753A GA500 Technical Manual
49
Figure 3.1 Standard Drive Connection Diagram
*1
Set the wiring sequence to de-energize the drive with the MFDO. If the drive outputs a fault during fault restart when you use the
fault restart function, set
L5-02 = 1 [Fault Contact at Restart Select = Always Active]
to de-energize the drive. Be careful when you
use a cut-off sequence. The default setting for
L5-02
is
0 [Active Only when Not Restarting]
.
*2
When you install a DC reactor, you must remove the jumper between ter1 and +2.