b5-14: PID Feedback Loss Detection Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-14
(01B2)
PID Feedback Loss
Detection Time
Sets the length of time that PID Feedback must be less than
b5-13 [PID Feedback Loss Detection
Lvl]
to detect
PID Feedback Loss [FbL]
.
1.0 s
(0.0 - 25.5 s)
■
b5-15: PID Sleep Function Start Level
No.
(Hex.)
Name
Description
Default
(Range)
b5-15
(01B3)
PID Sleep Function Start
Level
Sets the output level that triggers the PID Sleep function.
Determined by A1-02
(0.0 - 590.0)
The drive goes into Sleep mode when the PID output or frequency reference is less than
b5-15
for longer than the
time set to
b5-16 [PID Sleep Delay Time]
. The drive continues operation when the PID output or frequency
reference is more than
b5-15
for longer than the time set to
b5-16
.
■
b5-16: PID Sleep Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-16
(01B4)
PID Sleep Delay Time
Sets a delay time to start or stop the PID Sleep function.
0.0 s
(0.0 - 25.5 s)
■
b5-17: PID Accel/Decel Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-17
(01B5)
RUN
PID Accel/Decel Time
Raises or lowers the PID setpoint using the acceleration and deceleration times set to the drive.
This is a soft-starter for the PID setpoint.
0.0 s
(0.0 - 6000.0 s)
The drive usually uses the acceleration and deceleration times set in
C1-xx [Accel and Decel Times]
, but when
PID control is enabled, the drive applies
C1-xx
after PID output. If you frequently change the PID setpoint, the
drive responsiveness decreases. When resonance with PID control causes hunting, overshoot, or undershoot, set
b5-17
for longer acceleration and deceleration times.
Decrease
C1-xx
until hunting stops, then use
b5-17
to check the acceleration and deceleration. To enable and
disable the setting in
b5-17
through an MFDI terminal, set
PID Soft Starter Disable [H1-xx = 34]
.
■
b5-18: b5-19 PID Setpoint Selection
No.
(Hex.)
Name
Description
Default
(Range)
b5-18
(01DC)
b5-19 PID Setpoint
Selection
Sets the function that enables and disables
b5-19 [PID Setpoint Value]
.
0
(0, 1)
0 : Disabled
The drive does not use the value set in
b5-19
as the PID setpoint.
1 : Enabled
The drive uses the value set in
b5-19
as the PID setpoint.
■
b5-19: PID Setpoint Value
No.
(Hex.)
Name
Description
Default
(Range)
b5-19
(01DD)
RUN
PID Setpoint Value
Sets the PID setpoint when
b5-18 = 1 [b5-19 PID Setpoint Selection = Enabled]
.
0.00%
(0.00 - 100.00%)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...