When you use
A1-03 [Initialize Parameters]
to initialize the drive, the drive will reset the manually set values
for
E3-04 to E3-13 [Motor 2 Base Voltage]
to default values.
■
E3-01: Motor 2 Control Mode Selection
No.
(Hex.)
Name
Description
Default
(Range)
E3-01
(0319)
Motor 2 Control Mode
Selection
Sets the control method for motor 2.
0
(0, 2)
Note:
•
When you change this setting, the drive will set all parameters that are dependent on
E3-01
to their default settings.
•
Parameter
L1-01 [Motor Overload (oL1) Protection]
sets the protection operation of
oL1 [Motor Overload]
the same as Motor 1.
•
When you use parameter
A1-03 [Initialize Parameters]
to initialize the drive, this parameter is not reset.
0 : V/f Control
2 : Open Loop Vector
■
E3-04: Motor 2 Maximum Output Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E3-04
(031A)
Motor 2 Maximum Output
Frequency
Set the maximum output frequency for the motor 2 V/f pattern.
Determined by E3-01
(40.0 - 590.0 Hz)
■
E3-05: Motor 2 Maximum Output Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E3-05
(031B)
Motor 2 Maximum Output
Voltage
Sets the maximum output voltage for the motor 2 V/f pattern.
Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
■
E3-06: Motor 2 Base Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E3-06
(031C)
Motor 2 Base Frequency
Sets the base frequency for the motor 2 V/f pattern.
Determined by E3-01
(0.0 - E3-04)
■
E3-07: Motor 2 Mid Point A Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E3-07
(031D)
Motor 2 Mid Point A
Frequency
Sets a middle output frequency for the motor 2 V/f pattern.
Determined by E3-01
(0.0 - E3-04)
■
E3-08: Motor 2 Mid Point A Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E3-08
(031E)
Motor 2 Mid Point A
Voltage
Sets a middle output voltage for the motor 2 V/f pattern.
Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
■
E3-09: Motor 2 Minimum Output Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E3-09
(031F)
Motor 2 Minimum Output
Frequency
Sets the minimum output frequency for the motor 2 V/f pattern.
Determined by E3-01
(0.0 - E3-04)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...