YASKAWA
SIEPC71061753A GA500 Technical Manual
557
Note:
Be aware of the following points when manually setting V/f patterns.
•
To set linear V/f characteristics at frequencies lower than
E1-06 [Base Frequency]
, set
E1-07 = E1-09 [Mid Point A Frequency =
Minimum Output Frequency]
. In this application, the drive ignores
E1-08 [Mid Point A Voltage]
.
•
Set the five frequencies as specified by these rules: Incorrect settings will cause
oPE10 [V/f Data Setting Error]
.
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04 [Minimum Output Frequency ≤ Mid Point A Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
•
Setting
E1-11 = 0 [Mid Point B Frequency = 0 Hz]
disables
E1-12 [Mid Point B Voltage]
. Ensure that the four frequencies are set
according to the following rules;
E1-09 ≤ E1-07 < E1-06 ≤ E1-04
•
When you use
A1-03 [Initialize]
to initialize the drive, it will not reset
E1-03
.
Figure 12.60 V/f Pattern
■
E1-01: Input AC Supply Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-01
(0300)
Input AC Supply Voltage
Sets the drive input voltage.
200 V Class: 230 V, 400 V:
400 V
(200 V Class: 155 to 255 V,
400 V Class: 310 to 510 V)
NOTICE:
Set parameter E1-01 to align with the drive input voltage (not motor voltage). If this parameter is incorrect, the
protective functions of the drive will not operate correctly and it can cause damage to the drive.
Values Related to the Drive Input Voltage
The value set in
E1-01
is the base value that the drive uses for the motor protective functions in
. With
a 400 V class drive, the detection level changes for some motor protective functions.
Table 12.46 Values Related to the Drive Input Voltage
Voltage
E1-01 Setting
Approximate Values
ov Detection Level
BTR Operation
Level
(rr Detection Level)
L2-05
[Undervoltage
Detection Lvl (Uv1)]
L2-11
[KEB DC Bus
Voltage Setpoint]
L3-17
[DC Bus Regulation
Level]
200 V class
All settings
410 V
394 V
190 V
260 V
375 V
400 V class
Setting value ≥ 400 V
820 V
788 V
380 V
500 V
750 V
Setting value < 400 V
820 V
788 V
350 V
460 V
750 V
*1
This is the protection function enabled in drives with built-in braking transistors. These values show the level that will trigger the
built-in braking transistor. Refer to
“
YASKAWA AC Drive 72060001 Series Option Braking Unit and Braking Resistor Unit
Installation Manual (TOBPC72060001)
”
for more information.
■
E1-03: V/f Pattern Selection
No.
(Hex.)
Name
Description
Default
(Range)
E1-03
(0302)
V/f Pattern Selection
Sets the V/f pattern for the drive and motor. You can use one of the preset patterns or you can
make a custom pattern.
F
(Determined by A1-02)
Note:
•
When
A1-02 = 2 [Control Method Selection = OLV]
, settings
0
to
E
are not available.
•
Set the correct V/f pattern for the application and operation area. An incorrect V/f pattern can decrease motor torque and increase
current from overexcitation.
•
Parameter
A1-03 [Initialize Parameters]
will not reset the value of
E1-03
.
0 : Const Trq, 50Hz base, 50Hz max
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...