SIEPC71061753A GA500 Technical Manual
679
■
L2-09: KEB Minimum Frequency Level
No.
(Hex.)
Name
Description
Default
(Range)
L2-09
(048D)
Expert
KEB Minimum Frequency
Level
Sets the quantity of output frequency reduction used as a percentage of
E2-02 [Motor Rated Slip]
when KEB operation starts.
20%
(0 - 100%)
These conditions set the quantity of decrease:
•
Motor rated slip × (
L2-09
/100)
•
The larger value between the value calculated with
L2-08
and the value calculated with
L2-09
■
L2-10: Minimum KEB Time
No.
(Hex.)
Name
Description
Default
(Range)
L2-10
(048E)
Expert
Minimum KEB Time
Sets the minimum length of time to operate the KEB after the drive detects a momentary power
loss.
50 ms
(0 - 25500 ms)
When you return power while KEB is operating, the drive continues KEB operation until the time set in
L2-10
is
expired. When the DC bus voltage is less than the level of
L2-05 [Undervoltage Detect Level (Uv1)]
in one of
these conditions, KEB operation continues until the time set in
L2-10
is expired:
•
L2-01 = 3 [Momentary Power Loss Ope Select = KEB Mode].
•
L2-01 = 4 [KEB Stop Mode]
•
L2-01 = 5 [KEB Decel to Stp].
•
KEB Ride-Thru 1/2 [H1-xx = 65, 66, 7A, or 7B] is input into the drive.
When you input KEB Ride-Thru, KEB operation continues after the time set in
L2-10
is expired. When you
cancel KEB Ride-Thru, the motor accelerates again. When you do not input KEB Ride-Thru during the time set in
L2-10
, the drive accelerates to the frequency reference that the drive had before power loss in the applicable
acceleration time.
When
L2-01 = 3, 4, or 5
, and the DC bus voltage is a minimum of the value of
L2-11 [DC Bus Vol Setpoint during
KEB]
, the drive accelerates again after the time set in
L2-10
is expired. If the DC bus voltage is less than the
L2-
11
value, KEB operation continues after the time set in
L2-10
is expired.
Note:
•
When
L2-01 = 0, 1, or 2 [Disabled, Enabled, or Enabled when CPU is Running]
, increase the value of
L2-10
. Set
L2-10
to cancel
KEB operation if the KEB Ride-Thru is not input
•
Set this parameter to 0 to disable the function.
■
L2-11: KEB DC Bus Voltage Setpoint
No.
(Hex.)
Name
Description
Default
(Range)
L2-11
(0461)
Expert
KEB DC Bus Voltage
Setpoint
Sets the target value that controls the DC bus voltage to a constant level in Single Drive KEB
Ride-Thru 2. Sets the DC bus voltage level that completes the KEB operation for all other KEB
methods.
Determined by E1-01
(Determined by E1-01)
■
L2-29: Kinetic Energy Backup Method
No.
(Hex.)
Name
Description
Default
(Range)
L2-29
(0475)
Expert
Kinetic Energy Backup
Method
Sets the KEB function operation mode.
0
(0 - 3)
Set
L2-01 = 3, 4, or 5 [Momentary Power Loss Ope Select = KEB Mode, KEB Stop Mode, or KEB Decel to Stp]
or
KEB Ride-Thru 1/2 [H1-xx = 65, 66, 7A, or 7B]
, to enable the KEB function.
0 : Single Drive KEB Ride-Thru 1
The drive monitors the DC bus voltage and uses regenerative energy from the motor to hold the DC bus voltage at
the level set in
L2-11 [KEB DC Bus Voltage Setpoint]
.
The KEB operation continues and the deceleration rate changes as specified by
C1-09 [Fast Stop Time]
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...