Table 3.8 Control Circuit Monitor Output Terminals
Type
Terminal
Name (Default)
Function (Signal Level)
Monitor Output
MP
Pulse train output
(Output frequency)
32 kHz (maximum)
Refer to
“
Pulse Train Output
”
(page
) for more informaion.
AM
Analog monitor output
(Output frequency)
Select voltage or current output.
•
0 V to 10 V/0% to 100%
•
4 mA to 20 mA (Receiver recommended impedance: 250 Ω)
Note:
Select using jumper switch S5 and
H4-07 [Terminal AM Sign
al Level Select].
AC
Monitor common
0 V
■
External Power Supply Input Terminals
Refer to
for a list of the functions of the external power supply input terminals.
Table 3.9 External Power Supply Input Terminals
Type
Terminal
Name (Default)
Function
External Power Supply Input
Terminals
PS
External 24 V power supply input
Supplies backup power to the drive control circuit, keypad, and option board.
21.6 VDC to 26.4 VDC, 700 mA
AC
External 24 V power supply ground
0 V
Alarm Display When You Use External 24 V Power Supply
When you use an external 24 V power supply, an alarm is detected as shown in
if you set
o2-23
[External 24V Powerloss Detection]
and
o2-26 [Alarm display at ext. 24V power]
for the main circuit power
supply. Set the alarm display as needed.
Table 3.10 Power Supply Used and the Alarm Display
Main circuit power supply
External 24 V power supply
o2-23
[External 24V Powerloss
Detection]
o2-26
[Alarm display at ext. 24V
power]
Alarm display
ON
ON
-
-
-
ON
OFF
0 [Disabled]
-
-
1 [Enabled]
-
L24v [Loss of External Power 24
Supply]
OFF
ON
-
0 [Disabled]
"Ready" LED light flashes
quickly
-
1 [Enabled]
EP24v [External Power 24V
Supply]
■
Serial Communication Terminals
Refer to
for a list of serial communication terminals and functions.
Table 3.11 Serial Communication Terminals
Type
Terminal
Terminal Name
Function (Signal Level)
Modbus Communication
D+
Communication
input/output (+)
MEMOBUS/Modbus communications
Use an RS-485 cable to connect the drive.
Note:
Set DIP switch S2 to ON to enable the
termination resistor in the last drive in a
MEMOBUS/Modbus network.
•
RS-485
•
MEMOBUS/Modbus communication protocol
•
Maximum 115.2 kbps
D-
Communication
output (-)
AC
Signal ground
0 V
◆
Control Circuit Terminal Configuration
The control circuit terminals are in the positions shown in
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...