SIEPC71061753A GA500 Technical Manual
Code
Name
Causes
Possible Solutions
oPE10
V/f Data Setting Error
The parameters that set the V/f pattern do not
satisfy these conditions:
•
For motor 1:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤
E1-04 [Minimum Output Frequency ≤ Mid Point
A Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
•
For motor 2:
E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤
E3-04 [Minimum Output Frequency ≤ Mid Point
A Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
Set the parameters correctly to satisfy the conditions.
Code
Name
Causes
Possible Solutions
oPE11
Carrier Frequency Setting Error
These parameters are set at the same time:
•
C6-05 > 6 [Carrier Freq Proportional Gain >
6]
•
C6-04 > C6-03 [Carrier Frequency Lower Limit
> Carrier Frequency Upper Limit]
Note:
When
C6-05 < 7
,
C6-04
becomes disabled. The
drive sets the carrier frequency to the value set
to
C6-03
.
C6-02 to C6-05
settings are not in the applicable
setting range.
Set
C6-02 to C6-05
correctly.
Code
Name
Causes
Possible Solutions
oPE13
Pulse Monitor Selection Error
H6-06 = 101, 102, 105, or 116 [Terminal MP
Monitor Selection = Frequency Reference, Output
Frequency, Motor Speed, Output Frequency after
Soft Starter]
has not been set when
H6-07 = 0
[Terminal MP Frequency Scaling = 0 Hz]
.
Set
H6-06
correctly.
Code
Name
Causes
Possible Solutions
oPE16
Energy Saving Constants Error
The Energy Saving parameters are not set in the
applicable setting range.
Make sure that
E5-xx
is set correctly as specified by the motor
nameplate data.
Code
Name
Causes
Possible Solutions
oPE33
Digital Output Selection Error
These two parameters are set at the same time:
•
H2-60 ≠ F [Term MA,MB,MC Secondary
Function ≠ Not Used]
•
H2-01 = 1xx [Term MA,MB,MC Function
Selection = Inverse output of xx]
These two parameters are set at the same time:
•
H2-63 ≠ F [Terminal P1 Secondary Function ≠
Not Used]
•
H2-02 = 1xx [Term P1 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
•
H2-66 ≠ F [Terminal P2 Secondary Function ≠
Not Used]
•
H2-03 = 1xx [Term P2 Function Selection =
Inverse output of xx]
Clear the
H2-01 to H2-03 = 1xx [Inverse output of xx]
settings.
Note:
If you use the function to output logical calculation results
(
H2-60, H2-63, H2-66 ≠ F
), you cannot set
H2-01 to H2-03 =
1xx
.
These parameter pairs are set incorrectly:
•
H2-21 [Comparator 1 Lower Limit]
>
H2-22
[Comparator 1 Upper Limit]
•
H2-27 [Comparator 2 Lower Limit]
>
H2-28
[Comparator 2 Upper Limit]
•
Set parameters
H2-21
≤
H2-22
.
•
Set parameters
H2-27
≤
H2-28
.
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...