![YASKAWA CIPR-GA50C series Technical Manual Download Page 533](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765533.webp)
YASKAWA
SIEPC71061753A GA500 Technical Manual
533
Figure 12.46 Proportional Gain through Multi-function Digital Input Switch
■
Speed Waveform Monitoring Method
To make small adjustments of ASR parameters, monitor the speed waveforms when you make the adjustments.
shows example settings of parameters to monitor speed waveforms.
Table 12.38 Example Settings of MFAO Terminals to Monitor Speed Waveforms
No.
Name
Setting Value
Description
H4-01
Terminal AM Analog Output Select
116
Lets you use terminal AM to monitor
U1-
16 [SFS Output Frequency]
.
H4-02
Terminal AM Analog Output Gain
100.0%
H4-03
Terminal AM Analog Output Bias
0.0%
H4-07
Terminal AM Signal Level Select
0
Lets you monitor in a 0 V to 10 V range.
Based on this setting, MFAO terminal AM outputs the output frequency after SFS in a 0 V to 10 V (0% to 100%)
range. The MFAO common is terminal AC:
Yaskawa recommends that you monitor the output frequency after SFS and the motor speed for delays in response
and differences in reference values.
■
Adjust ASR Parameters
Use
to adjust ASR. The table lists parameters for motor 1. You can make the same changes to motor 2
parameters when you run a second motor.
Note:
When adjusting the proportional gain and integral time, adjust the proportional gain first.
Table 12.39 ASR Response and Possible Solutions
Problem
Possible Solutions
Speed response is slow.
•
Increase
C5-01/C5-03 [ASR Proportional Gain]
.
•
Decrease
C5-02/C5-04 [ASR Integral Time]
.
Overshoot or undershoot occurs at the end of acceleration
or deceleration.
•
Decrease
C5-01/C5-03
.
•
Increase
C5-02/C5-04
.
Vibration and oscillation occur at constant speed.
•
Decrease
C5-01/C5-03
.
•
Increase
C5-02/C5-04
.
•
Increase
C5-06 [ASR Delay Time]
.
Oscillation at low speed and response is too slow at high
speed.
Oscillation at high speed and response is too slow at low
speed.
-
When
A1-02 = 6 [Control Method Selection = AOLV/
PM]
, use
C5-01 to C5-04
to set the best ASR settings for
high and low speed. Use
C5-07 [ASR Gain Switchover
Frequency]
to switch the ASR proportional gain and ASR
integral time as specified by the output frequency.
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...