11.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
YASKAWA
SIEPC71061753A GA500 Technical Manual
427
No.
Name
Range
Unit
Control Method (A1-02 Setting)
OLV/PM
(5)
AOLV/PM
(6)
EZOLV
(8)
b3-09
Speed Estimation ACR I
Time
0.0 - 1000.0
0.1 ms
4.0
4.0
4.0
b3-14
Bi-directional Speed
Search
0 - 1
1
-
-
0
b5-15
PID Sleep Function Start
Level
0.0 - 400.0
0.1
0.0 Hz
0.0%
0.0%
b6-01
Dwell Reference at Start
0.0 - 400.0
0.1
0.0 Hz
0.0%
0.0%
b6-03
Dwell Reference at Stop
0.0 - 400.0
0.1
0.0 Hz
0.0%
0.0%
b8-02
Energy Saving Gain
0.0 - 10.0
0.1
-
-
-
b8-03
Energy Saving Filter Time
0.00 - 10.00
0.01 s
-
-
-
b8-19
E-Save Search Injection
Freq
10 - 300
1 Hz
100
100
20
C1-11
Accel/Decel Time
Switchover Freq
0.0 - 400.0
0.1
0.0 Hz
0.0%
0.0%
C2-01
S-Curve Time @ Start of
Accel
0.00 - 10.00
0.01 s
1.00
0.20
1.00
C3-01
Slip Compensation Gain
0.0 - 2.5
0.1
-
-
0
C3-02
Slip Compensation Delay
Time
0 - 10000
1 ms
-
-
200
C4-01
Torque Compensation
Gain
0.00 - 2.50
0.01
0.00
-
0.00
C4-02
Torque Compensation
Delay Time
0 - 10000
1 ms
100
-
100
C5-01
ASR Proportional Gain 1
0.00 - 300.00
0.01
10.00
10.00
10.00
C5-02
ASR Integral Time 1
0.000 - 60.000
0.001 s
0.500
0.500
0.500
C5-03
ASR Proportional Gain 2
0.00 - 300.00
0.01
-
10.00
10.00
C5-04
ASR Integral Time 2
0.000 - 10.000
0.001 s
-
0.500
0.500
C5-06
ASR Delay Time
0.000 - 0.500
0.001 s
-
0.016
0.004
C5-07
ASR Gain Switchover
Frequency
0.0 - 400.0
0.1
0.0Hz
0.0%
0.0%
C6-02
Carrier Frequency
Selection
1 - F
1
2
2
2
d3-01
Jump Frequency 1
0.0 - 400.0
0.1
0.0 Hz
0.0%
0.0%
d3-02
Jump Frequency 2
0.0 - 400.0
0.1
0.0 Hz
0.0%
0.0%
d3-03
Jump Frequency 3
0.0 - 400.0
0.1
0.0 Hz
0.0 %
0.0 %
d3-04
Jump Frequency Width
0.0 - 20.0
0.1
1.0 Hz
1.0 %
1.0 %
E1-04
Maximum Output
Frequency
40.0 - 400.0
0.1 Hz
Determined by E5-01
Determined by E5-01
Determined by E5-01
E1-05
Maximum Output Voltage
0.0 - 255.0
0.1 V
Determined by E5-01
Determined by E5-01
Determined by E5-01
E1-06
Base Frequency
0.0 - 400.0
0.1 Hz
Determined by E5-01
Determined by E5-01
Determined by E5-01
E1-07
Mid Point A Frequency
0.0 - 400.0
0.1 Hz
-
-
-
E1-08
Mid Point A Voltage
0.0 - 255.0
0.1 V
-
-
-
E1-09
Minimum Output
Frequency
0.0 - 400.0
0.1 Hz
Determined by E5-01
Determined by E5-01
Determined by E5-01
E1-10
Minimum Output Voltage
0.0 - 255.0
0.1 V
-
-
-
F1-09
Overspeed Detection
Delay Time
0.0 - 2.0
0.1 s
-
0.0
-
L1-01
Motor Overload (oL1)
Protection
0 - 4
1
4
4
Determined by E9-01
L2-31
KEB Start Voltage Offset
Level
0 - 100
1 V
50
50
50
L3-05
Stall Prevention during
RUN
0 - 3
1
1
-
3
L3-20
DC Bus Voltage
Adjustment Gain
0.00 - 5.00
0.01
0.65
0.65
0.65
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...