![YASKAWA CIPR-GA50C series Technical Manual Download Page 350](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765350.webp)
350
YASKAWA
SIEPC71061753A GA500 Technical Manual
◆
C4: Torque Compensation
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
C4-01
(0215)
RUN
Torque Compensation
Gain
Sets the gain for the torque compensation function. Use this parameter value for motor
1 when operating multiple motors.
Note:
When
A1-02 = 8 [Control Method Selection = EZOLV]
, you cannot change this
parameter during drive run.
Determined by A1-02
(0.00 - 2.50)
C4-02
(0216)
RUN
Torque Compensation
Delay Time
Sets the torque compensation delay time. Usually it is not necessary to change this
setting.
Note:
If
A1-02 = 8 [Control Method Selection = EZOLV]
, you cannot change the setting
while the drive is running.
Determined by A1-02
(0 - 60000 ms)
C4-03
(0217)
Torque Compensation @
FWD Start
Set the amount of torque reference for forward start as a percentage of the motor rated
torque.
0.0%
(0.0 - 200.0%)
C4-04
(0218)
Torque Compensation @
REV Start
Sets the amount of torque reference for reverse start as a percentage of the motor rated
torque.
0.0%
(-200.0 - 0.0%)
C4-05
(0219)
Torque Compensation
Time
Sets the starting torque constant to use with
C4-03 and C4-04 [Torque Compensation @
FWD/REV Start]
.
10 ms
(0 - 200 ms)
C4-06
(021A)
Motor 2 Torque Comp
Delay Time
Sets the value if
ov [Overvoltage]
occurs with sudden changes in the load, at the end of
acceleration, or at the start of deceleration.
150 ms
(0 - 10000 ms)
C4-07
(0341)
RUN
Motor 2 Torque
Compensation Gain
Sets the gain for motor 2 torque compensation function when using the Motor Switch
function.
1.00
(0.00 - 2.50)
C4-23
(1583)
RUN
Expert
Current Control Gain
Current control gain. Usually it is not necessary to change this parameter.
1.00
(0.50 - 2.50)
◆
C5: Automatic Speed Regulator (ASR: Automatic Speed Regulator)
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
C5-01
(021B)
RUN
ASR Proportional Gain 1
Sets the gain to adjust ASR response.
Note:
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
Determined by A1-02
(0.00 - 300.00)
C5-02
(021C)
RUN
ASR Integral Time 1
Sets the ASR integral time.
Note:
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
Determined by A1-02
(0.000 - 60.000 s)
C5-03
(021D)
RUN
ASR Proportional Gain 2
Sets the gain to adjust ASR response.
Note:
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
Determined by A1-02
(0.00 - 300.00)
C5-04
(021E)
RUN
ASR Integral Time 2
Sets the ASR integral time.
Note:
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
Determined by A1-02
(0.000 - 60.000 s)
C5-05
(021F)
ASR Limit
Sets the ASR output limit where
E1-04 [Maximum Output Frequency]
is 100%.
Note:
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
5.0%
(0.0 - 20.0%)
C5-06
(0220)
ASR Delay Time
Sets the filter time constant of the torque reference output from the speed loop. Usually
it is not necessary to change this setting.
Determined by A1-02
(0.000 - 0.500 s)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...