SIEPC71061753A GA500 Technical Manual
■
b6-04: Dwell Time at Stop
No.
(Hex.)
Name
Description
Default
(Range)
b6-04
(01B9)
Dwell Time at Stop
Sets the length of time for the drive to hold the output frequency when ramping to stop the motor.
0.0 s
(0.0 - 10.0 s)
◆
b8: Energy Saving
Energy-saving control improves overall system operating efficiency by operating the motor at its most efficient
level.
Set
b8-01
and these parameters according to the control method and the motor.
•
When you use V/f Control, set parameters
b8-04 to b8-06
.
•
When you use vector control with an induction motor, set parameters
b8-02 and b8-03
.
•
When you use a PM motor, set parameters
b8-16 and b8-17
.
Note:
•
Energy-saving control is not appropriate for applications with sudden changes in the load, or applications driving heavy loads such as a
traverse car application.
•
Energy-saving control maximizes operation based on precise motor data set to the drive. Make sure that you do Auto-Tuning and enter
the correct information about the motor before you use the Energy-saving control.
■
b8-01: Energy Saving Control Selection
No.
(Hex.)
Name
Description
Default
(Range)
b8-01
(01CC)
Energy Saving Control
Selection
Sets the Energy-saving control function.
0
(0 - 2)
0 : Disabled
1 : Enabled
2 : Automatic Optimization
Note:
When
A1-02 = 6 [Control Method Selection = AOLV/PM]
, you can only select setting
2
in Expert Mode.
■
b8-02: Energy Saving Gain
No.
(Hex.)
Name
Description
Default
(Range)
b8-02
(01CD)
RUN
Expert
Energy Saving Gain
Sets the gain for Energy-saving control.
Determined by A1-02
(0.0 - 10.0)
Increase the setting value to increase energy saving. If the setting value is too large, the motor will stall.
■
b8-03: Energy Saving Filter Time
No.
(Hex.)
Name
Description
Default
(Range)
b8-03
(01CE)
RUN
Expert
Energy Saving Filter Time
Sets the responsiveness for Energy-saving control.
Determined by A1-02
,
C6-
01 and o2-04
(0.00 - 10.00 s)
Decrease the setting value to increase responsiveness. If the setting value is too low, operation will not be stable.
■
b8-04: Energy Saving Coefficient Value
No.
(Hex.)
Name
Description
Default
(Range)
b8-04
(01CF)
Expert
Energy Saving Coefficient
Value
Sets the Energy-saving control coefficient to maintain maximum motor efficiency. The default
setting is for Yaskawa motors.
Determined by C6-01, E2-
11, and o2-04
(0.00 - 655.00)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...