584
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
F6-01: Communication Error Selection
No.
(Hex.)
Name
Description
Default
(Range)
F6-01
(03A2)
Communication Error
Selection
Sets the method to stop the motor or let the motor continue operating when the drive detects
bUS
[Option Communication Error]
.
1
(0 - 5)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. The output terminal set for
Fault [H2-01 to H2-03 =
E]
activates.
1 : Coast to Stop
The output turns off and the motor coasts to stop. The output terminal set for
Fault [H2-01 to H2-03 = E]
activates.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in
C1-09 [Fast Stop Time]
. The output terminal set for
Fault
[H2-01 to H2-03 = E]
activates.
3 : Alarm Only
The keypad shows
bUS
and the drive continues operation at the current frequency reference.
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
The output terminal set to
Alarm [H2-01 to H2-03 = 10]
activates.
4 : Alarm (Run at d1-04)
The keypad shows
bUS
and the drive continues operation at the speed set in
d1-04 [Reference 4]
.
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
5 : Alarm - Ramp Stop
The drive stops the motor during the deceleration time set in
C1-02 [Deceleration Time 1]
.
After you remove the
bUS
alarm, the motor will accelerate to the previous frequency reference.
■
F6-02: Comm External Fault (EF0) Detect
No.
(Hex.)
Name
Description
Default
(Range)
F6-02
(03A3)
Comm External Fault (EF0)
Detect
Sets the conditions at which
EF0 [Option Card External Fault]
is detected.
0
(0, 1)
0 : Always Detected
1 : Detected during RUN Only
■
F6-03: Comm External Fault (EF0) Select
No.
(Hex.)
Name
Description
Default
(Range)
F6-03
(03A4)
Comm External Fault (EF0)
Select
Sets the method to stop the motor or let the motor continue operating when the drive detects
EF0
[Option Card External Fault]
.
1
(0 - 3)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. The output terminal set for
Fault [H2-01 to H2-03 =
E]
activates.
1 : Coast to Stop
The output turns off and the motor coasts to stop. The output terminal set for
Fault [H2-01 to H2-03 = E]
activates.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in
C1-09 [Fast Stop Time]
. The output terminal set for
Fault
[H2-01 to H2-03 = E]
activates.
3 : Alarm Only
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...