12.8 H: Terminal Function Selection
YASKAWA
SIEPC71061753A GA500 Technical Manual
603
When terminal S1 (Run command) activates for 1 ms minimum, the drive rotates the motor. When terminal S2
(Stop command) deactivates, the drive stops. When terminal Sx that is set in 3-wire sequence deactivates, the
drive operates in the forward direction, and when it activates, the drive operates in the reverse direction.
WARNING!
Sudden Movement Hazard. Set the MFDI parameters before you close control circuit switches. Incorrect Run/Stop
circuit sequence settings can cause serious injury or death from moving equipment.
WARNING!
Sudden Movement Hazard. When you use a 3-Wire sequence, set A1-03 = 3330 [Initialize Parameters = 3-Wire
Initialization] and make sure that b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command] (default). If you
do not correctly set the drive parameters for 3-Wire operation before you energize the drive, the motor can suddenly rotate in
reverse when you energize the drive.
Figure 12.64 3-Wire Sequence Wiring Example
.
Figure 12.65 3-Wire Sequence Time Chart
Note:
•
To input the Run command, activate the terminal for 1 ms minimum.
•
The default setting for
b1-17 [Run Command at Power Up]
is
0 [Disregard existing RUN command]
. If you enable the Run command
when the drive is energized, the protective function activates and the
flashes quickly. When the application allows Run, set
b1-
17 = 1 [Accept Existing RUN Command]
.
■
1: LOCAL/REMOTE Selection
Setting Value
Function
Description
1
LOCAL/REMOTE
Selection
Sets drive control for the keypad (LOCAL) or an external source (REMOTE).
Note:
•
When the MFDI terminal sets the LOCAL/REMOTE selection,
on the keypad is disabled.
•
When LOCAL Mode is selected, the green light for
comes on.
•
When the Run command is ON, you cannot switch between LOCAL Mode and REMOTE Mode.
ON : LOCAL
The keypad is the Frequency reference source and Run command source.
OFF : REMOTE
The frequency reference and Run command settings are set in
b1-01
,
b1-02 [Frequency Reference Selection 1/2]
or
b1-15
,
b1-16 [Run Command Selection 1/2]
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...