12.11 o: Keypad-Related Settings
738
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
o2-04: Drive Model (KVA) Selection
No.
(Hex.)
Name
Description
Default
(Setting Range)
o2-04
(0508)
Drive Model (KVA)
Selection
Sets the Drive Model code. Set this parameter after replacing the control board.
Determined by the drive
(-)
NOTICE:
Set o2-04 [Drive Model Selection] correctly. If you set this parameter incorrectly, it will decrease drive performance,
cause the protection function to operate incorrectly, and cause damage to the drive.
Note:
When the setting value of
o2-04
changes, related parameter setting values also change. Refer to
Defaults by Drive Model and Duty
for more information.
These tables list the relation between
o2-04
setting values and drive models.
o2-04 Setting
Drive Model
30
B001
31
B002
32
B004
33
B006
34
B010
35
B012
37
B018
60
2001
61
2002
62
2004
63
2006
64
2008
65
2010
66
2012
67
2018
68
2021
91
2030
o2-04 Setting
Drive Model
92
2042
93
2056
94
2070
95
2082
96
4001
97
4002
99
4004
6A
4005
6B
4007
6D
4009
6E
4012
6F
4018
9A
4023
9C
4031
9D
4038
9E
4044
9F
4060
■
o2-05: Home Mode Freq Ref Entry Mode
No.
(Hex.)
Name
Description
Default
(Setting Range)
o2-05
(0509)
Home Mode Freq Ref Entry
Mode
Sets the function that makes it necessary to push
to use the keypad to change the frequency
reference value while in Drive Mode.
0
(0, 1)
0 : ENTER Key Required
You must push
to use the keypad to change the frequency reference value.
1 : Immediate / MOP-style
The frequency reference changes when you enter it with the keypad. This then changes the output frequency. It is
not necessary to push
. The drive keeps the frequency reference for 5 seconds after you use
and
on
the keypad to change the frequency reference value.
■
o2-06: Keypad Disconnect Detection
No.
(Hex.)
Name
Description
Default
(Range)
o2-06
(050A)
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive
or if you damage the cable while the keypad is the Run command source.
0
(0, 1)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...