![YASKAWA CIPR-GA50C series Technical Manual Download Page 662](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765662.webp)
12.8 H: Terminal Function Selection
662
YASKAWA
SIEPC71061753A GA500 Technical Manual
Note:
•
Refer to H1-xx "MFDI Setting Values" for more information on the virtual digital input setting values.
•
Refer to H2-xx "MFDO Setting Values" for more information on the virtual digital output setting values.
•
Refer to H3-xx "MFAI Setting Values" for more information on the virtual analog input setting values.
•
Refer to H4-xx "MFAO Setting Values" for more information on the virtual analog output setting values.
•
You cannot set
0 [3-Wire Sequence]
and
20 or 2F [External Fault]
to
H7-01 to H7-04 [Virtual Multi-Function Input 1 to 4]
.
•
If the terminal is not used, set
H7-01 to H7-04 = F
. However, the through mode function is not supported.
■
H7-00: Virtual MFIO selection
No.
(Hex.)
Name
Description
Default
(Range)
H7-00
(116F)
Expert
Virtual MFIO selection
Sets the function to enable and disable the virtual I/O function. Set this parameter to 1 to operate
the virtual I/O function.
0
(0, 1)
0 : Disabled
1 : Enabled
■
H7-01: Virtual Multi-Function Input 1
No.
(Hex.)
Name
Description
Default
(Range)
H7-01
(1185)
Expert
Virtual Multi-Function
Input 1
Sets the function that enters the virtual input set in
H7-10 [Virtual Multi-Function Output 1]
.
F
(1 - 19F)
■
H7-02: Virtual Multi-Function Input 2
No.
(Hex.)
Name
Description
Default
(Range)
H7-02
(1186)
Expert
Virtual Multi-Function
Input 2
Sets the function that enters the virtual input set in
H7-12 [Virtual Multi-Function Output 2]
.
F
(1 - 19F)
■
H7-03: Virtual Multi-Function Input 3
No.
(Hex.)
Name
Description
Default
(Range)
H7-03
(1187)
Expert
Virtual Multi-Function
Input 3
Sets the function that enters the virtual input set in
H7-14 [Virtual Multi-Function Output 3]
.
F
(1 - 19F)
■
H7-04: Virtual Multi-Function Input 4
No.
(Hex.)
Name
Description
Default
(Range)
H7-04
(1188)
Expert
Virtual Multi-Function
Input 4
Sets the function that enters the virtual input set in
H7-16 [Virtual Multi-Function Output 4]
.
F
(1 - 19F)
■
H7-10: Virtual Multi-Function Output 1
No.
(Hex.)
Name
Description
Default
(Range)
H7-10
(11A4)
Expert
Virtual Multi-Function
Output 1
Sets the function for virtual digital output 1.
F
(0 - 1A7)
■
H7-11: Virtual Output 1 Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H7-11
(11A5)
Expert
Virtual Output 1 Delay
Time
Sets the minimum ON time for virtual digital output 1.
0.1 s
(0.0 - 25.0 s)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...