![YASKAWA CIPR-GA50C series Technical Manual Download Page 366](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765366.webp)
366
YASKAWA
SIEPC71061753A GA500 Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F7-04
(03E8)
IP Address 4
Sets the fourth octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When
F7-13 = 0 [Address Mode at Startup = Static]
:
•
Use parameters
F7-01 to F7-04 [IP Address 4]
to set the IP Address. Be sure to set
a different IP address for each drive on the network.
•
Also set parameters
F7-01 to F7-12
.
20
(0 - 255)
F7-05
(03E9)
Subnet Mask 1
Sets the first octet of the subnet mask of the connected network.
Note:
Set this parameter when
F7-13 = 0 [Address Mode at Startup = Static]
.
255
(0 - 255)
F7-06
(03EA)
Subnet Mask 2
Sets the second octet of the subnet mask of the connected network.
Note:
Set this parameter when
F7-13 = 0 [Address Mode at Startup = Static]
.
255
(0 - 255)
F7-07
(03EB)
Subnet Mask 3
Sets the third octet of the subnet mask of the connected network.
Note:
Set this parameter when
F7-13 = 0 [Address Mode at Startup = Static]
.
255
(0 - 255)
F7-08
(03EC)
Subnet Mask 4
Sets the fourth octet of the subnet mask of the connected network.
Note:
Set this parameter when
F7-13 = 0 [Address Mode at Startup = Static]
.
0
(0 - 255)
F7-09
(03ED)
Gateway Address 1
Sets the first octet of the gateway address of the connected network.
Note:
Set this parameter when
F7-13 = 0 [Address Mode at Startup = Static]
.
192
(0 - 255)
F7-10
(03EE)
Gateway Address 2
Sets the second octet of the gateway address of the connected network.
Note:
Set this parameter when
F7-13 = 0 [Address Mode at Startup = Static]
.
168
(0 - 255)
F7-11
(03EF)
Gateway Address 3
Sets the third octet of the gateway address of the connected network.
Note:
Set this parameter when
F7-13 = 0 [Address Mode at Startup = Static]
.
1
(0 - 255)
F7-12
(03F0)
Gateway Address 4
Sets the fourth octet of the gateway address of the connected network.
Note:
Set this parameter when
F7-13 = 0 [Address Mode at Startup = Static]
.
1
(0 - 255)
F7-13
(03F1)
Address Mode at Startup
Sets the method to set option card IP addresses.
0 : Static
1 : BOOTP
2 : DHCP
Note:
•
The following setting values are available when using the PROFINET
communication option card (SI-EP3).
–
0: Static
–
2: DHCP
•
When
F7-13 = 0
, set parameters
F7-01 to F7-12 [IP Address 1 to Gateway
Address 4]
to set the IP Address. Be sure to set a different IP address for each
drive on the network.
2
(0 - 2)
F7-14
(03F2)
Duplex Mode Selection
Sets the duplex mode setting method.
0 : Half/Half
1 : Auto/Auto
2 : Full/Full
3 : Half/Auto
4 : Half/Full
5 : Auto/Half
6 : Auto/Full
7 : Full/Half
8 : Full/Auto
1
(0 - 8)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...