496
YASKAWA
SIEPC71061753A GA500 Technical Manual
Set this parameter as a ratio of
E2-03 [Motor No-Load Current]
. The setting is a ratio with respect to 30% of the
motor rated current when
E2-03
≤
E2-01 [Motor Rated Current]
× 0.3.
Note:
The setting is a ratio with respect to
E9-06 [Motor Rated Current (FLA)]
× 0.5 when
A1-02 = 8 [Control Method Selection = EZOLV]
.
■
b3-32: Spd Search Current Complete Lvl
No.
(Hex.)
Name
Description
Default
(Range)
b3-32
(0BC1)
Expert
Spd Search Current
Complete Lvl
Sets the current level that completes Speed Search.
1.20
(0.00 - 1.49)
The Current Detection Speed Search gradually decreases the output frequency to search for the motor speed when
the output current is equal to or less than Speed Search Current Complete Level.
Set this parameter as a ratio of
E2-03 [Motor No-Load Current]
. The setting is a ratio with respect to 30% of the
motor rated current when
E2-03
≤
E2-01 [Motor Rated Current]
× 0.3.
Note:
The setting is a ratio with respect to
E9-06 [Motor Rated Current (FLA)]
× 0.5 when
A1-02 = 8 [Control Method Selection = EZOLV]
.
■
b3-33: Speed Search during Uv Selection
No.
(Hex.)
Name
Description
Default
(Range)
b3-33
(0B3F)
Expert
Speed Search during Uv
Selection
Sets the function that starts Speed Search at start-up if the drive detects a
Uv [Undervoltage]
when it receives a Run command.
1
(0, 1)
Set these three parameters as shown to enable
b3-33
:
•
L2-01 = 1, 2 [Power Loss Ride Through Select = Enabled for L2-02 Time, Enabled while CPU Power Active]
•
b3-01 = 1 [Speed Search at Start Selection = Enabled]
•
b1-03 = 1 [Stopping Method Selection = Coast to Stop]
0 : Disabled
1 : Enabled
■
b3-54: Search Time
No.
(Hex.)
Name
Description
Default
(Range)
b3-54
(3123)
Search Time
Sets the length of time that the drive will run Speed Search.
400 ms
(10 - 2000 ms)
If you set this parameter too low, Speed Search will not operate correctly.
If the drive detects
oC [Overcurrent]
immediately after Speed Search Starts:
•
Increase the value of
L2-03 [Minimum Baseblock Time]
and decrease the motor speed you use to start Speed
Search.
•
Increases the setting value of
b3-08 [Speed Estimation ACR P Gain]
.
•
Increase the value of
b3-54
.
If the drive detects
oC
or
ov [DC Bus Overvoltage]
during Speed Search, increase the value of
b3-08
.
■
b3-55: Current Increment Time
No.
(Hex.)
Name
Description
Default
(Range)
b3-55
(3124)
Expert
Current Increment Time
Sets the length of time that the drive will increase the current from zero current to the setting
value of
b3-06 [Speed Estimation Current Level 1]
.
10 ms
(10 - 2000 ms)
Gradually increase the setting value when a large quantity of current flows after speed search starts. If you set this
value too high, speed search will not operate correctly.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...