SIEPC71061753A GA500 Technical Manual
If you set
n5-03 [Feed Forward Control Gain]
too high, the motor speed will momentarily increase to more than
the set frequency.
◆
n6: Online Tuning
n6 parameters
are used to set the online tuning function for motor line-to-line resistance.
The Online Tuning for motor line-to-line resistance is used to prevent degradation of speed control accuracy due
to motor temperature fluctuation and motor stalls due to insufficient torque.
■
n6-01: Online Tuning Selection
No.
(Hex.)
Name
Description
Default
(Range)
n6-01
(0570)
Online Tuning Selection
Sets the type of motor data that Online Tuning uses for OLV control.
0
(0 - 2)
0 : Disabled
1 : Line-to-Line Resistance Tuning
The drive adjusts the motor line-to-line resistance during run. This procedure is applicable for speed values 6 Hz
and less. It also adjusts the motor resistance value to increase the overload capacity in the low speed range.
2 : Voltage Correction Tuning
The drive adjusts the output voltage during run to increase overload tolerance and minimize the effects of high
temperatures on speed precision.
Note:
Setting 2 is enabled only when
b8-01 = 0 [Energy Saving Control Selection = Disabled]
.
■
n6-05: Online Tuning Gain
No.
(Hex.)
Name
Description
Default
(Range)
n6-05
(05C7)
Expert
Online Tuning Gain
Sets the compensation gain when
n6-01 = 2 [Online Tuning Selection = Voltage Correction
Tuning]
. Usually it is not necessary to change this parameter.
1.0
(0.1 - 50.0)
When you use a motor that has a large secondary circuit time constant, decrease the setting value.
If the drive detects
oL1 [Motor Overload]
, increase the setting value in 0.1-unit increments.
◆
n7: EZ Drive
The
n7 parameters
provide special adjustments for EZ Vector Control.
■
n7-01: Damping Gain for Low Frequency
No.
(Hex.)
Name
Description
Default
(Range)
n7-01
(3111)
Expert
Damping Gain for Low
Frequency
Sets the oscillation suppression gain for the low speed range.
1.0
(0.1 - 10.0)
Note:
•
If oscillation occurs in the low speed range, increase the acceleration time or increase the setting value in 0.5-unit increments.
•
To get starting torque with the setting for
C4-01 [Torque Compensation Gain]
, decrease the setting value in 0.3-unit increments.
■
n7-05: Response Gain for Load Changes
No.
(Hex.)
Name
Description
Default
(Range)
n7-05
(3115)
Expert
Response Gain for Load
Changes
Sets the response gain related to changes in the load.
50
(10 - 1000)
Note:
To make tracking related to load changes better, increase the setting value in 5-unit increments. If oscillation occurs during load
changes, decrease the setting value in 5-unit increments.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...