Logical Operation Selection
Logical Operation Expression
Logical Operation Notation
H2-61, H2-64, H2-67
5
A != B
6
AND(A, )
7
OR(A, )
8
-
On
Note:
•
If you use the function to output logical calculation results, you cannot set
H2-01 to H2-03 = 1xx [Inverse Output of xx]
. If you do, the
drive will detect
oPE33 [Digital Output Selection Error]
.
•
When you do not use
H2-60, H2-63, and H2-66
, set them to
F
. The through mode function is not supported.
◆
H2 MFDO Parameters
■
H2-01: Term MA/MB-MC Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-01
(040B)
Term MA/MB-MC
Function Selection
Sets the function set for MFDO terminal MA-MC or MB-MC.
E
(0 - 1FF)
Note:
Set this parameter to
F
when the terminal is not being used or to use the terminal in through mode.
■
H2-02: Term P1-C1 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-02
(040C)
Term P1-C1 Function
Selection
Sets the function for MFDO terminal P1-C1.
0
(0 - 1FF)
Note:
Set this parameter to
F
when the terminal is not being used or to use the terminal in through mode.
■
H2-03: Term P2-C2 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-03
(040D)
Term P2-C2 Function
Selection
Sets the function for MFDO terminal P2-C2.
2
(0 - 1FF)
Note:
Set this parameter to
F
when the terminal is not being used or to use the terminal in through mode.
■
H2-06: Watt Hour Output Unit Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-06
(0437)
Watt Hour Output Unit
Selection
Sets the unit for the output signal when
H2-01 to H2-03 = 39 [MFDO Function Selection = Watt
Hour Pulse Output]
.
0
(0 - 4)
This output is input to the Watt hour meter or PLC through a 200 ms pulse signal. This parameter sets the kWh
unit for each pulse output.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...