12.8 H: Terminal Function Selection
606
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
E: ASR Integral Reset
Setting Value
Function
Description
E
ASR Integral Reset
Sets the command to reset the integral value and use PI control or P control for the speed control loop.
ON : P control
OFF : PI control
■
F: Not Used
Setting Value
Function
Description
F
Not Used
Use this setting for unused terminals or to use terminals in through mode.
Through Mode uses the signal input to the terminal as a digital input for the upper sequence through a
communication option or MEMOBUS/Modbus communications. This input signal does not have an effect on
drive operation.
■
10: Up Command
Setting Value
Function
Description
10
Up Command
Sets the command to use a push button switch to increase the drive frequency reference. You must also set
Setting 11 [Down
Command]
.
ON : Increases the frequency reference.
OFF : Holds the current frequency reference.
Note:
•
If you set only the Up command or only the Down command, the drive will detect
oPE03 [Multi-Function Input Setting Err]
.
•
If you set two or more of these functions at the same time, the drive will detect
oPE03
:
–
Up/Down command
–
Accel/Decel Ramp Hold
–
Reference Sample Hold
–
Offset Frequency 1, 2, 3 addition
–
Up/Down 2 Command
•
The Up/Down command does not function in these conditions:
–
b1-01 = 2, 3 [Frequency Reference Selection 1 = Memobus/Modbus Communications, Option PCB]
–
b1-02 ≠ 1 [Run Command Selection 1 ≠ Control Circuit Terminal]
–
Drive is in LOCAL mode
–
Set to
b1-15 [Frequency Reference Selection 2]
by use of
H1-xx = 2 [MFDI Function Select = External Reference 1/2 Selection]
When you enter the UP command, the frequency reference increases. When you enter the Down command, the
frequency reference decreases.
The Up and Down commands have priority over all other frequency references. When you enable the Up/Down
command, the drive will ignore these frequency references:
•
Frequency reference from Keypad
[b1-01 = 0]
•
Frequency reference from Analog Input
[b1-01 = 1]
•
Frequency reference from Pulse Train Input
[b1-01 = 4]
shows the Up and Down commands with their operation.
Table 12.56 Up Command and Down Command
Command status
Drive operation
Up command (10)
Down command (11)
OFF
OFF
Keeps the current frequency reference.
ON
OFF
Increases the frequency reference.
OFF
ON
Decreases the frequency reference.
ON
ON
Keeps the current frequency reference.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...