12.8 H: Terminal Function Selection
YASKAWA
SIEPC71061753A GA500 Technical Manual
631
Figure 12.80 Frequency Detection 1 Time Chart
Note:
shows the result of the configuration when
L4-07 = 1 [Speed Agree Detection Selection = Detection Always Enabled]
. The
default setting of
L4-07
is
0 [No detection during baseblock]
. When the speed agreement detection selection is
“
No Detection during
Baseblock
”
, the terminal is deactivated when the drive output stops.
■
5: Frequency Detection 2
Setting Value
Function
Description
5
Frequency Detection 2
The terminal activates when the output frequency is higher than the value of
L4-01 [Speed Agree Detection Level]
. After the
terminal activates, the terminal stays activated until the output frequency is at the value of
L4-01
-
L4-02
.
Note:
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the forward/reverse detection
level.
ON : The output frequency is higher than the value of
L4-01
.
OFF : The output frequency is less than the value of “
L4-01
-
L4-02
,” or it is not more than the
value of
L4-01
.
Figure 12.81 Frequency Detection 2 Time Chart
■
6: Drive ready
Setting Value
Function
Description
6
Drive ready
The terminal activates when the drive is ready and running.
The terminal deactivates in these conditions:
•
When the power supply is OFF
•
During a fault
•
When there is problem with the control power supply
•
When there is a parameter configuration error and the drive cannot operate although there is a Run command
•
When you enter a Run command and it immediately triggers an overvoltage or undervoltage fault because the
drive has an overvoltage or undervoltage fault during stop
•
When the drive is in Programming Mode and will not accept a Run command
■
7: DC Bus Undervoltage
Setting Value
Function
Description
7
DC Bus Undervoltage
The terminal activates when the DC bus voltage or control circuit power supply is less than the voltage set with
L2-05
[Undervoltage Detection Lvl (Uv1)]
. The terminal also turns on when there is a fault with the DC bus voltage.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...