708
YASKAWA
SIEPC71061753A GA500 Technical Manual
Set
L8-40 ≠ 0.00
to enable the carrier frequency reduction function during start-up. When operation starts, the
drive automatically decreases the carrier frequency. When the time set in
L8-40
is expired, the carrier frequency
returns to the value set in
C6-02 [Carrier Frequency Selection]
.
■
L8-41: High Current Alarm Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-41
(04F2)
High Current Alarm
Selection
Sets the function to cause an
HCA [Current Alarm]
when the output current is more than 150% of
the drive rated current.
0
(0, 1)
0 : No
The drive will not detect
HCA
.
1 : Yes
If the output current is more than 150% of the drive rated current, the drive will detect
HCA
.
The MFDO terminal set for an
Alarm [H2-01 to H2-03 = 10]
activates.
■
L8-51: STPo I Detection Level
No.
(Hex.)
Name
Description
Default
(Range)
L8-51
(0471)
Expert
STPo I Detection Level
Sets the
STPo [Motor Step-Out Detected]
detection level as a percentage of the motor rated
current.
0.0%
(0.0 - 300.0%)
Note:
The detection level is automatically calculated when
L8-51 = 0
.
■
L8-52: STPo Integration Level
No.
(Hex.)
Name
Description
Default
(Range)
L8-52
(0472)
Expert
STPo Integration Level
Sets the detection level for
STPo [Motor Step-Out Detected]
related to the ACR integral value.
1.0
(0.1 - 2.0)
■
L8-53: STPo Integration Time
No.
(Hex.)
Name
Description
Default
(Range)
L8-53
(0473)
Expert
STPo Integration Time
Sets the length of time until the drive detects
STPo
after it is more than the value of
L8-51 [STPo I
Detection Level]
.
1.0 s
(1.0 - 10.0 s)
■
L8-54: STPo Id Diff Detection
No.
(Hex.)
Name
Description
Default
(Range)
L8-54
(0474)
Expert
STPo Id Diff Detection
Sets the Id deviation detection function for
STPo [Motor Step-Out Detected]
.
1
(0, 1)
0 : Disabled
1 : Enabled
■
L8-55: Internal DB TransistorProtection
No.
(Hex.)
Name
Description
Default
(Range)
L8-55
(045F)
Internal DB
TransistorProtection
Sets the protection function for the internal braking transistor.
1
(0, 1)
0 : Disable
Disables braking transistor protection.
Use this setting, if enabling the braking transistor can cause an
rF [Braking Resistor Fault]
in these conditions:
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...