![YASKAWA CIPR-GA50C series Technical Manual Download Page 575](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765575.webp)
YASKAWA
SIEPC71061753A GA500 Technical Manual
575
Auto-Tuning automatically sets this parameter to the value of [Number of Motor Poles].
■
E9-09: Motor Rated Slip
No.
(Hex.)
Name
Description
Default
(Range)
E9-09
(11EC)
Motor Rated Slip
Sets the motor rated slip.
0.000 Hz
(0.000 - 20.000 Hz)
The setting value of this parameter is the slip compensation reference value.
The drive uses the setting values of
E9-03
,
E9-04
, and
E9-08
to calculate this parameter. When Motor Rated Slip
= 0, Auto-Tuning automatically sets this parameter to the value of [Motor Rated Slip].
Note:
Set
E9-01 = 0 [Motor Type Selection = Induction (IM)]
before you set this parameter.
■
E9-10: Motor Line-to-Line Resistance
No.
(Hex.)
Name
Description
Default
(Range)
E9-10
(11ED)
Motor Line-to-Line
Resistance
Sets the line-to-line resistance for the motor stator windings.
Determined by o2-04
(0.000 - 65.000 Ω)
Note:
This value is the motor line-to-line resistance. Do not set this parameter with the single-phase resistance.
Stationary Auto-Tuning automatically sets this parameter. If you cannot do Stationary Auto-Tuning, use the test
report from the motor manufacturer. You can calculate the motor line-to-line resistance with one of these
formulas:
•
E-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
•
B-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
•
F-type insulation: the resistance value (Ω) shown on the test report at 115 °C × 0.87
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...