![YASKAWA CIPR-GA50C series Technical Manual Download Page 740](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765740.webp)
12.11 o: Keypad-Related Settings
740
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
o2-26: Alarm display at ext. 24V power
No.
(Hex.)
Name
Description
Default
(Range)
o2-26
(1563)
Alarm display at ext. 24V
power
When you connect a backup external 24 V power supply, this parameter sets the function to
trigger an alarm when the main circuit power supply voltage decreases.
0
(0, 1)
0 : Disabled
The drive will not detect
EP24v [External Power 24V Supply]
if the main circuit power supply voltage decreases.
The [Ready] light on the LED Status Ring flashes quickly to identify that drive operation is not possible.
1 : Enabled
The drive detects
EP24v
when the main circuit power supply voltage decreases.
Note:
The minor fault signal is not output from
H2-xx = 10 [MFDO Function Selection = Alarm]
.
■
o2-27: bCE Detection Selection
No.
(Hex.)
Name
Description
Default
(Range)
o2-27
(1565)
bCE Detection Selection
Sets drive operation if the Bluetooth device is disconnected when you operate the drive in
Bluetooth Mode.
3
(0 - 4)
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : No Alarm Display
◆
o3: Copy Function
o3 parameters
set the operation of the parameter backup function.
■
o3-01: Copy Keypad Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
o3-01
(0515)
Copy Keypad Function
Selection
Sets the function that saves and copies drive parameters to a different drive with the keypad.
0
(0 - 4)
0 : Copy Select
1 : Backup (drive → keypad)
The parameter setting values are read from the drive and saved in the keypad.
2 : Restore (keypad → drive)
Copies the parameter setting values saved in the keypad to a different drive.
3 : Verify (check for mismatch)
Makes sure that the parameter setting values in the drive agree with the parameters saved in the keypad.
4 : Erase (backup data of keypad)
Deletes the parameter setting values saved in the keypad.
■
o3-02: Copy Allowed Selection
No.
(Hex.)
Name
Description
Default
(Range)
o3-02
(0516)
Copy Allowed Selection
Sets the copy function when
o3-01 = 1 [Copy Keypad Function Selection = Backup (drive →
keypad)]
.
0
(0, 1)
Note:
When you select [Parameter Backup] on the keypad menu screen to do the backup function, the drive automatically sets
o3-02 = 1
.
0 : Disabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...