12.8 H: Terminal Function Selection
604
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
2: External Reference 1/2 Selection
Setting Value
Function
Description
2
External Reference 1/2
Selection
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in REMOTE Mode.
Note:
When the drive is receiving a Run command, you cannot switch between reference sources.
ON :
b1-15 = [Frequency Reference Selection 2], b1-16 [Run Command Selection 2]
OFF :
b1-01 = [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]
■
3: Multi-Step Speed Reference 1
Setting Value
Function
Description
3
Multi-Step Speed Reference
1
Uses speed references
d1-01 to d1-16
to set a multi-step speed reference.
Note:
Refer to
“
Setting Procedures for Multi-step Speed Operation
”
in
“
d: Reference Settings
”
for more information.
■
4: Multi-Step Speed Reference 2
Setting Value
Function
Description
4
Multi-Step Speed Reference
2
Uses speed references
d1-01 to d1-16
to set a multi-step speed reference.
Note:
Refer to
“
Setting Procedures for Multi-step Speed Operation
”
in
“
d: Reference Settings
”
for more information.
■
5: Multi-Step Speed Reference 3
Setting Value
Function
Description
5
Multi-Step Speed Reference
3
Uses speed references
d1-01 to d1-16
to set a multi-step speed reference.
Note:
Refer to
“
Setting Procedures for Multi-step Speed Operation
”
in
“
d: Reference Settings
”
for more information.
■
6: Jog Reference Selection
Setting Value
Function
Description
6
Jog Reference Selection
Sets the drive to use the JOG Frequency Reference (JOG command) set in
d1-17
. The JOG Frequency Reference (JOG
command) overrides Frequency References
1 to 16 (d1-01 to d1-16)
.
■
7: Accel/Decel Time Selection 1
Setting Value
Function
Description
7
Accel/Decel Time Selection
1
Sets the drive to use
Acceleration/Deceleration Time 1 [C1-01, C1-02]
or
Acceleration/Deceleration Time 2 [C1-03, C1-04]
.
Note:
Refer to
“
C1: Accel & Decel Time
”
for more information.
■
8: Baseblock Command (N.O.)
Setting Value
Function
Description
8
Baseblock Command
(N.O.)
Sets the command that stops drive output and coasts the motor to stop when the input is ON.
The keypad flashes
bb [Baseblock]
. If you cancel the baseblock command when the Run command is active, the
drive will restart the motor and use the speed search function.
WARNING!
Sudden Movement Hazard. When you use a mechanical holding brake with the drive in a lifting application, you
must close the brake if an input terminal triggers the Baseblock command to stop drive output. If you enter the baseblock
command, the motor will suddenly coast and the load will slip, which can cause serious injury or death.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...