YASKAWA
SIEPC71061753A GA500 Technical Manual
295
◆
Alarm Outputs for Maintenance Monitors
You can use
H2-xx [MFDO Function Selection]
to send a message that tells you when a specified component is
near the end of its performance life estimate. Set the applicable value to
H2-xx
as shown in
for your
component.
When the specified component is near the end of its performance life estimate, the MFDO terminals set for
H2-xx
= 2F [Maintenance Notification]
will activate, and the keypad will show an alarm that identifies the component to
replace.
Table 8.9 Maintenance Period Alarms
Display
Alarm Name
Cause
Possible Solutions
Digital Outputs
(Setting Value in
H2-xx)
LT-1
Cooling Fan
Maintenance Time
The cooling fan is at 90% of its expected
performance life.
Replace the cooling fan, then set
o4-03 = 0 [Fan Operation
Time Setting = 0 h]
to reset the cooling fan operation time.
2F
LT-2
Capacitor
Maintenance Time
The capacitors for the main circuit and control
circuit are at 90% of expected performance life.
Replace the board or the drive.
Contact Yaskawa or your nearest sales representative to
replace the board.
LT-3
SoftChargeBypassRe
lay MainteTime
The soft charge bypass relay is at 90% of its
performance life estimate.
Replace the board or the drive.
Contact Yaskawa or your nearest sales representative to
replace the board.
LT-4
IGBT Maintenance
Time (50%)
The IGBT is at 50% of its expected performance
life.
Check the load, carrier frequency, and output frequency.
TrPC
IGBT Maintenance
Time (90%)
The IGBT is at 90% of its expected performance
life.
Replace the IGBT or the drive.
10
◆
Related Parameters
Replace the component, then set
o4-03, o4-05, o4-07, and o4-09 [Maintenance Setting] = 0
to reset the
Maintenance Monitor. If these parameters are not reset after the corresponding parts have been replaced, the
Maintenance Monitor function will continue to count down the performance life from the value that was reached
with the old part. If the Maintenance Monitor is not reset, the drive will not have the correct value of the
performance life for the new component.
Note:
The maintenance period changes for different operating environments.
Table 8.10 Maintenance Setting Parameters
No.
Name
Function
o4-03
Fan Operation Time Setting
Sets the value from which to start the cumulative drive cooling fan operation time in 10-hour units.
Note:
When
o4-03 = 30
has been set, the drive will count the operation time for the cooling fan from 300 hours
and
U4-03 [Cooling Fan Ope Time]
will show
300 h
.
o4-05
Capacitor Maintenance Setting
Sets the value from which to start the count for the main circuit capacitor maintenance period as a percentage.
o4-07
Softcharge Relay Maintenance Set
Sets as a percentage the value from which to start the count for the soft charge bypass relay maintenance
time.
o4-09
IGBT Maintenance Setting
Sets the value from which to start the count for the IGBT maintenance period as a percentage.
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...