d6: Field Weakening /Forcing
d6 parameters
set the field weakening and field forcing functions.
The field weakening function decreases the energy consumption of the motor. It decreases the output voltage of
the drive to a set level. The function decreases the motor excitation current inversely proportional to speed in a
constant output range, and does not let the induced voltage of the motor become more than the power supply
voltage. To enable this function, set
Field Weakening [H1-xx = 63]
ON.
Note:
Use the Field Weakening function in constant light-load applications. To control the energy consumption of the motor for other load
conditions, use the
b8 parameters [Energy Saving]
.
The Field Forcing function adjusts the delaying influence of the motor time constant when the drive changes the
excitation current reference and it also increases motor responsiveness. This function uses a high motor excitation
current reference for drive start-up only to help develop actual motor excitation current. Enable the Field Forcing
function to increase motor responsiveness.
Note:
You cannot use Field Forcing during DC Injection Braking.
■
d6-01: Field Weakening Level
No.
(Hex.)
Name
Description
Default
(Range)
d6-01
(02A0)
Field Weakening Level
Sets the drive output voltage as a percentage of
E1-05 [Maximum Output Voltage]
when
H1-xx =
63 [Field Weakening]
is activated.
80%
(0 - 100%)
■
d6-02: Field Weakening Frequency Limit
No.
(Hex.)
Name
Description
Default
(Range)
d6-02
(02A1)
Field Weakening Frequency
Limit
Sets the minimum output frequency to start field weakening.
0.0 Hz
(0.0 - 590.0 Hz)
Make sure that these two conditions are correct to enable the Field Weakening command:
•
The output frequency ≥
d6-02
.
•
There is a speed agreement status.
■
d6-03: Field Forcing Selection
No.
(Hex.)
Name
Description
Default
(Range)
d6-03
(02A2)
Field Forcing Selection
Sets the field forcing function.
0
(0, 1)
0 : Disabled
1 : Enabled
■
d6-06: Field Forcing Limit
No.
(Hex.)
Name
Description
Default
(Range)
d6-06
(02A5)
Field Forcing Limit
Sets the limit value for field forcing to increase the motor excitation current reference as a
percentage of
E2-03 [Motor No-Load Current]
. Usually it is not necessary to change this setting.
400%
(100 - 400%)
Note:
You cannot use Field Forcing during DC Injection Braking.
◆
d7: Offset Frequency
The drive will use 3 digital signal inputs, to add or subtract the set frequency (Offset frequency) to/from the
frequency reference and correct the speed. The drive uses the terminal set in
H1-xx = 44 to 46 [MFDI Function
Select = Add Offset Frequency 1 to 3]
to set the Offset frequency. When you close more than one input at the
same time, the drive adds the selected offset values together.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...