SIEPC71061753A GA500 Technical Manual
■
F6-51: DeviceNet Baud Rate
No.
(Hex.)
Name
Description
Default
(Range)
F6-51
(03C2)
DeviceNet Baud Rate
Sets the DeviceNet communications speed. Restart the drive after you change the parameter
setting.
0
(0 - 4)
0 : 125 kbps
1 : 250 kbps
2 : 500 kbps
3 : Adjustable from Network
The controller sets the communications speed.
4 : Detect Automatically
The drive detects the network communication speed and automatically adjusts the communications speed.
■
F6-52: DeviceNet PCA Setting
No.
(Hex.)
Name
Description
Default
(Range)
F6-52
(03C3)
DeviceNet PCA Setting
Sets the format of data that the DeviceNet communication master sends to the drive.
21
(0 - 255)
Note:
If
F6-52 [DeviceNet PCA Setting]
and
F6-53 [DeviceNet PPA Setting]
are not correct, the value is reset to default.
■
F6-53: DeviceNet PPA Setting
No.
(Hex.)
Name
Description
Default
(Range)
F6-53
(03C4)
DeviceNet PPA Setting
Sets the format of data that the drive sends to the DeviceNet communication master.
71
(0 - 255)
Note:
If
F6-52 [DeviceNet PCA Setting]
and
F6-53 [DeviceNet PPA Setting]
are not correct, the value is reset to default.
■
F6-54: DeviceNet Idle Fault Detection
No.
(Hex.)
Name
Description
Default
(Range)
F6-54
(03C5)
DeviceNet Idle Fault
Detection
Sets the function to detect
EF0 [Option Card External Fault]
when the drive does not receive
data from the DeviceNet master.
0
(0 - 4)
0 : Enabled
1 : Disabled, No Fault Detection
Does not detect
EF0
issues.
2 : Vendor Specific
3 : RUN Forward
4 : RUN Reverse
■
F6-55: DeviceNet Baud Rate Monitor
No.
(Hex.)
Name
Description
Default
(Range)
F6-55
(03C6)
DeviceNet Baud Rate
Monitor
Sets the function to see the actual DeviceNet communications speed using the keypad. This
parameter functions as a monitor only.
0
(0 - 2)
0 : 125 kbps
1 : 250 kbps
2 : 500 kbps
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...