![YASKAWA CIPR-GA50C series Technical Manual Download Page 530](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765530.webp)
530
YASKAWA
SIEPC71061753A GA500 Technical Manual
◆
C4: Torque Compensation
Torque compensation is a function that increases voltage to increase output torque as compensation for
insufficient torque production at start-up or low-speed operation.
Voltage drops due to motor winding resistance cause torque generating voltage to decrease, which causes
insufficient torque. If the main circuit cable connecting the drive and motor is long, this can also cause insufficient
torque due to voltage drops.
Note:
Set the motor parameters and V/f pattern properly before setting
C4 parameters
.
■
C4-01: Torque Compensation Gain
No.
(Hex.)
Name
Description
Default
(Range)
C4-01
(0215)
RUN
Torque Compensation Gain
Sets the gain for the torque compensation function. Use this parameter value for motor 1 when
operating multiple motors.
Determined by A1-02
(0.00 - 2.50)
For these control methods and states, adjust the setting value.
A1-02 [Control Method Selection]
Status
Adjustment
0 [V/f Control]
8 [EZ Vector Control]
Torque is not sufficient during low-speed operation of 10 Hz or less.
Increase the setting in 0.05-unit increments.
There is vibration in the motor or the motor hunts when operating the
drive with a light load.
Decrease the setting in 0.05-unit decrements.
The cable length between the drive and motor is too long.
Increase the setting in 0.05-unit increments.
Note:
•
Adjust
C4-01
to make sure that output current is not more than the drive rated current while the drive operates at low speed.
•
When
A1-02 = 2 [Open Loop Vector]
, do not change this parameter under normal conditions. Torque accuracy will decrease.
•
When
A1-02 = 5 [PM Open Loop Vector]
, do not change this parameter under normal conditions. Setting this value too high can cause
overcompensation and motor oscillation.
•
When
A1-02 = 8 [EZ Vector Control]
, you cannot change this parameter during drive run.
■
C4-02: Torque Compensation Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
C4-02
(0216)
RUN
Torque Compensation
Delay Time
Sets the torque compensation delay time. Usually it is not necessary to change this setting.
Determined by A1-02
(0 - 60000 ms)
Note:
If
A1-02 = 8 [Control Method Selection = EZOLV]
, you cannot change the setting while the drive is running.
Set this parameter in these conditions:
•
If there is vibration in the motor, increase the setting.
•
If the motor speed or motor torque response is too slow, decrease the setting.
■
C4-03: Torque Compensation @ FWD Start
No.
(Hex.)
Name
Description
Default
(Range)
C4-03
(0217)
Torque Compensation @
FWD Start
Set the amount of torque reference for forward start as a percentage of the motor rated torque.
0.0%
(0.0 - 200.0%)
The torque compensation function is performed using the time constant set in
C4-05 [Torque Compensation
Time]
.
This is available only when you start the motor with the forward command. Set this parameter to 0.0 to disable
this function.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...