12.11 o: Keypad-Related Settings
YASKAWA
SIEPC71061753A GA500 Technical Manual
739
This parameter continues to operate if the keypad installed to the drive becomes disconnected.
This parameter is enabled in these conditions:
•
When
b1-02 = 0 [Run Command Selection 1 = Keypad]
or
b1-16 = 0 [Run Command Selection 2 = Keypad]
•
In LOCAL Mode
0 : Disabled
The drive continues operation when it detects a keypad disconnection.
1 : Enabled
The drive stops operation, detects
oPr [Keypad Connection Fault]
, and the motor coasts to stop when the drive
detects a keypad disconnection.
■
o2-07: Keypad RUN Direction @ Power-up
No.
(Hex.)
Name
Description
Default
(Range)
o2-07
(0527)
Keypad RUN Direction @
Power-up
Sets the direction of motor rotation when the drive is energized and the keypad is the Run
command source.
0
(0, 1)
This parameter is enabled in these conditions:
•
When
b1-02 = 0 [Run Command Selection 1 = Keypad]
or
b1-16 = 0 [Run Command Selection 2 = Keypad]
•
In LOCAL Mode
0 : Forward
1 : Reverse
■
o2-09: Region Code
No.
(Hex.)
Name
Description
Default
(Range)
o2-09
(050D)
Reserved
-
-
■
o2-19: Parameter Write during Uv
No.
(Hex.)
Name
Description
Default
(Range)
o2-19
(061F)
Expert
Parameter Write during Uv
Lets you change parameters during
Uv [Undervoltage]
.
0
( 0, 1 )
0 : Disable
1 : Enabled
■
o2-23: External 24V Powerloss Detection
No.
(Hex.)
Name
Description
Default
(Setting Range)
o2-23
(11F8)
RUN
External 24V Powerloss
Detection
Sets the function to give a warning if the backup external 24 V power supply turns off when the
main circuit power supply is in operation.
0
(0, 1)
Note:
The drive will not run when it is operating from one 24-V external power supply.
0 : Disabled
The drive does not detect the loss of the 24-V external power supply.
1 : Enabled
The keypad shows the
L24v [Loss of External Power 24 Supply]
indicator when the drive detects the loss of the
24-V external power supply.
Note:
H2-xx = 10 [MFDO Function Selection = Minor Fault]
will not output a minor fault signal.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...