YASKAWA
SIEPC71061753A GA500 Technical Manual
591
■
F6-56: DeviceNet Speed Scaling
No.
(Hex.)
Name
Description
Default
(Range)
F6-56
(03D7)
DeviceNet Speed Scaling
Sets the speed scale for DeviceNet communication.
0
(-15 - +15)
■
F6-57: DeviceNet Current Scaling
No.
(Hex.)
Name
Description
Default
(Range)
F6-57
(03D8)
DeviceNet Current Scaling
Sets the current scale of the DeviceNet communication master.
0
(-15 - +15)
■
F6-58: DeviceNet Torque Scaling
No.
(Hex.)
Name
Description
Default
(Range)
F6-58
(03D9)
DeviceNet Torque Scaling
Sets the torque scale of the DeviceNet communication master.
0
(-15 - +15)
■
F6-59: DeviceNet Power Scaling
No.
(Hex.)
Name
Description
Default
(Range)
F6-59
(03DA)
DeviceNet Power Scaling
Sets the power scale of the DeviceNet communication master.
0
(-15 - +15)
■
F6-60: DeviceNet Voltage Scaling
No.
(Hex.)
Name
Description
Default
(Range)
F6-60
(03DB)
DeviceNet Voltage Scaling
Sets the voltage scale of the DeviceNet communication master.
0
(-15 - +15)
■
F6-61: DeviceNet Time Scaling
No.
(Hex.)
Name
Description
Default
(Range)
F6-61
(03DC)
DeviceNet Time Scaling
Sets the time scale of the DeviceNet communication master.
0
(-15 - +15)
■
F6-62: DeviceNet Heartbeat Interval
No.
(Hex.)
Name
Description
Default
(Range)
F6-62
(03DD)
DeviceNet Heartbeat
Interval
Sets the heartbeat for DeviceNet communication. Set this parameter to 0 to disable the heartbeat
function.
0
(0 - 10)
■
F6-63: DeviceNet Network MAC ID
No.
(Hex.)
Name
Description
Default
(Range)
F6-63
(03DE)
DeviceNet Network MAC
ID
Sets the function to see the actual DeviceNet MAC address using the keypad. This parameter
functions as a monitor only.
0
(0 - 63)
■
F6-64 to F6-67: Dynamic Out Assembly 109 Param1 to 4
No.
(Hex.)
Name
Description
Default
(Range)
F6-64 to F6-67
(03DF - 03E2)
Dynamic Out Assembly
109 Param 1 to 4
Sets Configurable Outputs 1 to 4 written to the MEMOBUS register.
0000h
(0000h - FFFFh)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...