12.8 H: Terminal Function Selection
YASKAWA
SIEPC71061753A GA500 Technical Manual
649
Figure 12.94 Stall Prevention Level during Run with Analog Input
■
9: Output Frequency Lower Limit
Setting Value
Function
Description
9
Output Frequency Lower
Limit
Enters a signal to adjust the output frequency lower limit level as a percentage of the maximum output frequency.
■
B: PID Feedback
Setting Value
Function
Description
B
PID Feedback
Enter the PID feedback value as a percentage of the maximum output frequency.
When you use this function, set
b5-01 = 1 to 8 [PID Mode Setting = Enabled]
.
■
C: PID Setpoint
Setting Value
Function
Description
C
PID Setpoint
Enters the PID setpoint as a percentage of the maximum output frequency.
When you use this function, set
b5-01 = 1 to 8 [PID Mode Setting = Enabled]
.
Note:
Configuring this function disables the frequency reference set with
b1-01 [Frequency Reference Selection 1]
.
■
D: Frequency Bias
Setting Value
Function
Description
D
Frequency Bias
Enters the bias value added to the frequency reference as a percentage of the maximum output frequency.
The drive adds the input value from the MFAI terminal set with this function to the frequency reference as the bias
value.
Note:
When you select
d1-01 to d1-16 or d1-17 [Reference 1 to 16 or JOG Frequency Reference]
as the frequency reference, it will disable
this function.
■
E: Motor Temperature (PTC Input)
Setting Value
Function
Description
E
Motor Temperature (PTC
Input)
Uses the motor Positive Temperature Coefficient (PTC) thermistor to prevent heat damage to the motor as a percentage of the
current value when the 10 V analog signal is input.
•
You can use the Positive Temperature Coefficient (PLC) thermistor as an auxiliary or alternative detection
function for
oL1 [Motor Overload]
problems to help prevent heat damage to motors. If the PTC input signal is
more than the overload alarm level,
oH3 [Motor Overheat (PTC Input)]
will flash on the keypad.
•
If the drive detects
oH3
, the motor stops with the method set in
L1-03
. If the drive detects
oH4
, the motor stops
with the method set in
L1-04
. If the drive incorrectly detects motor overheating problems, set
L1-05
.
■
F: Not Used
Setting Value
Function
Description
F
Not Used
Use this setting for unused terminals or to use terminals in through mode.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...