SIEPC71061753A GA500 Technical Manual
■
n8-76: Id Switching Filter Time
No.
(Hex.)
Name
Description
Default
(Range)
n8-76
(05CD)
Expert
Id Switching Filter Time
Sets the filter time constant for the d-axis current reference. Usually it is not necessary to change
this setting.
200 ms
(0 - 5000)
■
n8-77: Heavy Load Iq Level
No.
(Hex.)
Name
Description
Default
(Range)
n8-77
(05CE)
Expert
Heavy Load Iq Level
Set
n8-49 [Heavy Load Id Current]
to the percentage of load current (q-axis current) that you will
apply, where
E5-03 [Motor Rated Current (FLA)] = a setting value of 100%
.
90%
(0 - 255%)
Note:
The change is linear between
n8-75 [Medium Load Iq Level (low)]
and
n8-77
and the level of the pull-in current from
n8-78 [Medium
Load Id Current]
to
n8-49 [Heavy Load Id Current]
.
■
n8-78: Medium Load Id Current
No.
(Hex.)
Name
Description
Default
(Range)
n8-78
(05F4)
RUN
Expert
Medium Load Id Current
Sets the level of the pull-in current as a percentage, where
E5-03 [PM Motor Rated Current
(FLA)] = 100%
.
0%
(0 - 255%)
■
n8-79: Pull-in Current @ Deceleration
No.
(Hex.)
Name
Description
Default
(Range)
n8-79
(05FE)
Pull-in Current @
Deceleration
Sets the pull-in current that can flow during deceleration as a percentage of the
E5-03 [PM Motor
Rated Current (FLA)]
.
50%
(0 - 200%)
If overcurrent occurs during deceleration, slowly decrease the setting in 5% increments.
Note:
When
n8-79 = 0
, the drive will use the value set in
n8-51 [Pull-in Current @ Acceleration]
.
■
n8-84: Polarity Detection Current
No.
(Hex.)
Name
Description
Default
(Range)
n8-84
(02D3)
Expert
Polarity Detection Current
Sets the current that the drive uses to estimate the initial motor magnetic pole as a percentage
where
E5-03 [PM Motor Rated Current (FLA)] = 100%
.
100%
(0 - 150%)
WARNING!
Sudden Movement Hazard. Make sure that the polarity is correct before you send a Run command. If the drive
incorrectly detects the polarity, the drive can rotate in the direction opposite of the Run command and cause serious injury or
death.
When you use a Yaskawa motor, check the motor nameplate for an
“
Si
”
value and set this parameter ≥ "Si × 2".
Consult the motor manufacturer for information about maximum setting values.
Find the Polarity of Magnetic Poles
When you start operation, the drive estimates the magnetic poles and finds the polarity of the magnetic poles.
Use
U6-57 [PolePolarityDeterVal]
to make sure that the magnetic pole estimate was correct.
When you do High Frequency Injection Auto-Tuning, the drive automatically sets
n8-84
.
■
n8-87: Output Voltage Limit Selection
No.
(Hex.)
Name
Description
Default
(Range)
n8-87
(02BC)
Output Voltage Limit
Method
Sets the method of output voltage limit. If there is vibration in the constant output range, set
Feedforward Method. Usually it is not necessary to change this setting.
0
(0, 1)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...