Figure 12.63 Connection Examples in Gateway Mode
Table 12.49 Specification
Item
Specification
Applicable options
All options that support the MEMOBUS access function (for example, PROFIBUS-DP, PROFINET, EtherNet/IP, EtherCAT)
Compatible Products
Drives that can set F6-16 [Gateway Mode]
Number of connected drives
Maximum: 5 units
Communication specifications
MEMOBUS/Modbus (RTUmode) communications
Commands/responses
The controller can send this data to each drive (Drive 0 to Drive 4):
•
Control commands: Run commands and frequency references
•
Control responses: Output frequency and drive status (during run, faults)
•
Read and write parameters
•
Read monitors
Synchronous control
Not supported
*1
Gateway Mode is not available with Yaskawa 1000-series drives or previous series drives.
Note:
•
The communication speed in gateway mode is slower than the speed in fieldbus communications. Make sure that the speed is
acceptable for your system.
•
Response speed with the communication option is slower than with point-to-point communications.
•
Set
H5-03 [Communication Parity Selection]
to the same value on the master drive and slave drives.
WARNING!
Injury to Personnel. Separately prepare safety protection equipment and systems, for example fast stop switches. If
the motor does not stop correctly from the disconnection of communications cable or electrical interference, it can cause serious
injury.
Configuring Gateway Mode
shows sample settings to connect 4 slave drives:
Table 12.50 Sample Settings for Using Gateway Mode
F6-16
[Gateway Mode]
H5-01
[Drive Node
Address]
H5-02
[Communication
Speed Selection]
H5-03
[Communication
Parity Selection]
H5-06
[Drive Transmit
Wait Time]
H5-09
[CE Detection
Time]
b1-01
[Frequency
Reference
Selection 1]
b1-02
[Run Command
Selection 1]
Drive 0
(Master Drive)
1 - 4
1F (Default)
5 ms (factory
default)
≥ 2.0 s
3 [Option PCB]
3 [Option PCB]
Drive 1
(Slave drive)
0
5 ms (factory
default)
≥ 0.9 s
2 [Memobus/
Modbus
Communications]
2 [Memobus/
Modbus
Communications]
Drive 2
(Slave drive)
0
5 ms (factory
default)
≥ 0.9 s
2 [Memobus/
Modbus
Communications]
2 [Memobus/
Modbus
Communications]
Drive 3
(Slave drive)
0
5 ms (factory
default)
≥ 0.9 s
2 [Memobus/
Modbus
Communications]
2 [Memobus/
Modbus
Communications]
Drive 4
(Slave drive)
0
5 ms (factory
default)
≥ 0.9 s
2 [Memobus/
Modbus
Communications]
2 [Memobus/
Modbus
Communications]
*1
Restart the drive to apply the new settings.
*2
Specify the number of slave drives you will connect.
*3
Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
*4
Set a slave address that is different from other slave devices.
*5
Enter the same value that you use for the master drive.
*6
To correctly detect the response timeout, do not change the value of H5-06 from the default value.
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...