YASKAWA
SIEPC71061753A GA500 Technical Manual
581
*7
Set
H5-09 ≥ 0.9
. When
H5-09 < 0.9
, the drive will detect
CE [Modbus Communication Error]
before it detects a response timeout.
*8
On each slave drive, set
b1-01 [Frequency Reference Selection 1]
and
b1-02 [Run Command Selection 1]
to
2 [Memobus/Modbus
Communications]
.
An Overview of Gateway Mode
When in gateway mode, the drive will operate as shown in
.
A - Controller
B - Communication Option
C - Master Drive (Drive 0)
D - Slave Drives (Drives 1 to 4)
Table 12.51 Operation in Gateway Mode
Controller to Communication Option
Communication Option to Master Drive (Drive 0)
Master Drive (Drive 0) to Slave Drives (Drives 1 to
4)
•
The controller and card communicate in the format of
each field bus communications protocol.
•
Drive 0 sends commands and monitors through normal
field bus communications.
•
The special registers of Drive 0 use read and write to
send commands to and monitor Drives 1 to 4.
Field bus communication data is written to and read from
the special registers of Drive 0.
•
Uses MEMOBUS communications.
•
Drive 0 sends data from its special registers to Drives
1 to 4.
Operations at the Time of Communication Error
Communication Error
Error
Codes
Operation
From controller to
communication option
bUS
•
Master drive
Detects bUS
[Option Communication Error]
and operates as specified by
F6-01 [Communication Error Selection]
.
•
Slave drive
Detects
CE [Modbus Communication Error]
and operates as specified by
H5-04 [Communication Error Stop Method]
.
Note:
•
After error detection, each drive can continue the operation specified by the last received command if the
F6-01
and
H5-04
settings
agree. Because the controller cannot stop the operation, you must supply a stopping method, for example an emergency stop
switch.
•
If you set
H5-05 = 0 [Comm Fault Detection Selection = Disabled]
, the drive will not detect
CE
. The
H5-04
setting does not have
an effect.
From communication
option to master drive
oFAxx
•
Master drive
Detects
oFAxx
and coasts to stop.
•
Slave drive
Detects
hLCE [High Level Communication Errors]
and coasts to stop.
From master drive to
slave drive
CE
The master drive stops communicating with the slave drive in these conditions: Reset the fault to restart communication.
The slave drive detects
CE
after
H5-09 [CE Detection Time]
is expired. Then it operates in as specified with
H5-04 [Communication
Error Stop Method]
.
•
A message error occurred in the send data from the slave drive 10 consecutive times.
•
Response from the slave drive timed out 10 consecutive times.
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...