SIEPC71061753A GA500 Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
b5-12
(01B0)
Feedback Loss Detection
Select
Sets the drive response to PID feedback loss/excess. Sets drive operation after the drive
detects PID feedback loss/excess.
0 : Digital Out Only, Always Detect
1 : Alarm + Digital Out, Always Det
2 : Fault + Digital Out, Always Det
3 : Digital Out Only, @ PID Enable
4 : Alarm + Digital Out, @PID Enable
5 : Fault + Digital Out, @PID Enable
0
(0 - 5)
b5-13
(01B1)
PID Feedback Loss
Detection Lvl
Sets the level that triggers
PID Feedback Loss [FbL]
detection as a percentage of the
Maximum Output Frequency.
Note:
Parameter
A1-02 [Control Method Selection]
selects which parameter is the
maximum output frequency.
•
A1-02 ≠ 8 [EZOLV]
:
E1-04 [Maximum Output Frequency]
•
A1-02 = 8
:
E9-02 [Maximum Speed]
0%
(0 - 100%)
b5-14
(01B2)
PID Feedback Loss
Detection Time
Sets the length of time that PID Feedback must be less than
b5-13 [PID Feedback Loss
Detection Lvl]
to detect
PID Feedback Loss [FbL]
.
1.0 s
(0.0 - 25.5 s)
b5-15
(01B3)
PID Sleep Function Start
Level
Sets the output level that triggers the PID Sleep function.
Determined by A1-02
(0.0 - 590.0)
b5-16
(01B4)
PID Sleep Delay Time
Sets a delay time to start or stop the PID Sleep function.
0.0 s
(0.0 - 25.5 s)
b5-17
(01B5)
RUN
PID Accel/Decel Time
Raises or lowers the PID setpoint using the acceleration and deceleration times set to
the drive. This is a soft-starter for the PID setpoint.
0.0 s
(0.0 - 6000.0 s)
b5-18
(01DC)
b5-19 PID Setpoint
Selection
Sets the function that enables and disables
b5-19 [PID Setpoint Value]
.
0 : Disabled
1 : Enabled
0
(0, 1)
b5-19
(01DD)
RUN
PID Setpoint Value
Sets the PID setpoint when
b5-18 = 1 [b5-19 PID Setpoint Selection = Enabled]
.
0.00%
(0.00 - 100.00%)
b5-20
(01E2)
PID Unit Selection
Sets the number of digits to set and show the PID setpoint.
0 : 0.01Hz units
1 : 0.01% units
2 : min
-1
3 : User Units
1
(0 - 3)
b5-34
(019F)
RUN
PID Output Lower Limit
Level
Sets the output lower limit for the PID control as a percentage of the Maximum Output
Frequency.
Note:
Parameter
A1-02 [Control Method Selection]
selects which parameter is the
maximum output frequency.
•
A1-02 ≠ 8 [EZOLV]
:
E1-04 [Maximum Output Frequency]
•
A1-02 = 8
:
E9-02 [Maximum Speed]
0.0%
(-100.0 - +100.0%)
b5-35
(01A0)
RUN
PID Input Limit Level
Sets the output upper limit for the PID control as a percentage of the Maximum Output
Frequency.
Note:
Parameter
A1-02 [Control Method Selection]
selects which parameter is the
maximum output frequency.
•
A1-02 ≠ 8 [EZOLV]
:
E1-04 [Maximum Output Frequency]
•
A1-02 = 8
:
E9-02 [Maximum Speed]
1000.0%
(0.0 - 1000.0%)
b5-36
(01A1)
PID High Feedback
Detection Lvl
Sets the level that triggers
Excessive PID Feedback [FbH]
as a percentage of the
Maximum Output Frequency.
Note:
Parameter
A1-02 [Control Method Selection]
selects which parameter is the
maximum output frequency.
•
A1-02 ≠ 8 [EZOLV]
:
E1-04 [Maximum Output Frequency]
•
A1-02 = 8
:
E9-02 [Maximum Speed]
100%
(0 - 100%)
b5-37
(01A2)
PID High Feedback
Detection Time
Sets the length of time that the PID feedback signal must be more than the level set in
b5-36 [PID Feedback High Detection Lvl]
to cause
Excessive PID Feedback [FbH]
.
1.0 s
(0.0 - 25.5 s)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...