Note:
•
If the drive detects
Uv1 [DC Bus Undervoltage]
during KEB operation, decrease the value of
C1-09
.
•
If the drive detects
ov [Overvoltage]
during KEB operation, increase the value of
C1-09
.
1 : Single Drive KEB Ride-Thru 2
The drive does KEB operation and automatically calculates the deceleration rate to make sure that the main circuit
electrical energy and main current voltage from motor regenerative energy is equal to
L2-11 [DC Bus Vol Setpoint
during KEB]
.
2 : System KEB Ride-Thru 1
The drive does not monitor the DC bus voltage and decelerates as specified by the KEB deceleration time set in
L2-06
.
Set
L2-06
to the time necessary to decelerate from the frequency reference to 0 Hz when the drive detects a
momentary power loss. The drive can decelerate and keep constant deceleration rates for more than one drive.
Note:
If you keep constant deceleration rates for more than one drive, it can trigger
ov
faults. Use the dynamic braking option with System
KEB Ride-Thru 1 to prevent
ov
faults.
3 : System KEB Ride-Thru 2
The drive monitors the DC bus voltage and decelerates for the deceleration time set in
L2-06
.
If the DC bus voltage increases, the drive momentarily holds the frequency to prevent
ov
while deceleration
continues.
Note:
When you cannot use a dynamic braking option, use System KEB Ride-Thru.
■
L2-30: KEB Zero Speed Operation
No.
(Hex.)
Name
Description
Default
(Range)
L2-30
(045E)
Expert
KEB Zero Speed Operation
Sets the operation when the output frequency decreases below the zero level (DC braking
injection starting frequency) during KEB deceleration when
L2-01 = 3 to 5 [Power Loss Ride
Through Select = Kinetic Energy Backup: L2-02, Kinetic Energy Backup: CPU Power, or Kinetic
Energy Backup: DecelStop]
.
0
(0, 1)
0 : Baseblock
1 : DC/SC Braking
Does DC injection braking and short circuit braking as specified by
b2-04 [DC Inject Braking Time at Stop]
and
b2-13 [Short Circuit Brake Time @ Stop]
.
■
L2-31: KEB Start Voltage Offset Level
No.
(Hex.)
Name
Description
Default
(Range)
L2-31
(045D)
Expert
KEB Start Voltage Offset
Level
Sets the KEB start voltage offset.
Determined by A1-02
(200 V Class: 0 - 100 V,400
V Class: 0 - 200 V)
The drive uses this formula to calculate the KEB start voltage:
KEB start voltage =
L2-05 [Undervoltage Detect Level (Uv1)] + L2-31
◆
L3: Stall Prevention
L3 parameters
set the Stall Prevention function and overvoltage suppression function.
■
Stall Prevention
If the load is too heavy or the acceleration and deceleration times are too short, the motor can slip too much
because it cannot work at the same rate as the frequency reference. If the motor stalls during acceleration, current
increases as the slip increases to cause an
oC [Overcurrent]
,
oL2 [Drive Overload]
, or
oL1 [Motor Overload]
and
the drive will stop. If the motor stalls during deceleration, too much regenerative power will flow back into the
DC bus capacitors, and cause the drive to fault out from
ov [Overvoltage]
and the drive will stop.
The stall prevention function will let the motor get to the set speed without stalling and it is not necessary for you
to change the acceleration or deceleration time settings. You can set a separate stall prevention functions for
acceleration, operating at constant speeds, and deceleration.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...