12.8 H: Terminal Function Selection
YASKAWA
SIEPC71061753A GA500 Technical Manual
659
2 : PID Setpoint Value
The drive inputs the PID control target value received from terminal RP.
3 : Speed Feedback (V/F Control)
Select V/f Control method to enable simple encoder feedback.
Use motor speed feedback for better speed control precision. The drive compares the frequency reference to the
motor speed feedback received from the encoder, and uses the ASR function to compensates for motor slip. You
cannot use input terminal RP used for the simple encoder to detect the direction of motor rotation. Use a different
method to detect motor rotation.
Use these methods to detect the direction of motor rotation.
•
Use MFDI
Set MFDI
H1-xx = 7E [Reverse Rotation Identifier]
. When the configured terminal is activated, the motor
operates in Reverse run. When the terminal is deactivated, the motor operates in Forward run.
Use an encoder that outputs 2-tracks (phase A, B) to detect the direction of motor rotation.
•
Use the frequency reference
When the you do not use the MFDI, the Forward/Reverse run command is the same as the direction of motor
rotation.
shows speed control in Simple Closed Loop V/f Mode.
Figure 12.101 Simple Closed Loop Speed Control Block Diagram
Enable Simple Closed Loop V/f Mode
1. Connect the encoder output pulse wiring to terminal RP.
2. Set
A1-02 = 0 [Control Method Selection = V/f Control]
.
3. Set
H6-01 = 3
.
4. Set
H6-02 [Terminal RP Frequency Scaling]
to the speed feedback (pulse train input signal) frequency at the
time when the frequency reference is 100%.
Make sure that
H6-04 [Terminal RP Function Bias]
= 0% and
H6-03 [Terminal RP Function Gain]
= 100%.
5. Select the detection method for the direction of motor rotation.
When you use an MFDI, set
H1-xx = 7E
.
6. Set
C5 parameters
related to ASR gain and integral time to adjust responsiveness.
Note:
•
Set
A1-02 = 0
and
H6-01 = 3
to show
C5 parameters
.
•
You cannot use Closed Loop V/f Control mode with the Motor Switch function.
■
H6-02: Terminal RP Frequency Scaling
No.
(Hex.)
Name
Description
Default
(Range)
H6-02
(042D)
RUN
Terminal RP Frequency
Scaling
Sets the frequency of the pulse train input signal used when the item selected with
H6-01
[Terminal RP Pulse Train Function]
is input at 100%.
1440 Hz
(100 - 32000 Hz)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...