![YASKAWA CIPR-GA50C series Technical Manual Download Page 419](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765419.webp)
YASKAWA
SIEPC71061753A GA500 Technical Manual
419
No.
(Hex.)
Name
Description
MFAO Signal Level
U4-13
(07CF)
Peak Hold Current
Shows the hold value of the peak value (rms) for the drive output current.
Use
U4-14 [PeakHold Output Freq]
to show the drive output frequency at the time that the drive
holds the output current.
The drive will hold the peak hold current at the next start up and restart of the power supply. The
drive keeps the value that was under hold during baseblock (during stop).
The keypad shows the value of
U4-13
in amperes (A). When looking at the monitor through
MEMOBUS/Modbus communications, the current is
“
8192 = drive rated current (A)
”
. Calculate
the current from the monitor value that is in at MEMOBUS/Modbus communications using
“
Numerals being displayed / 8192 × drive rated current (A).
Unit: When the drive model changes, the display units for this parameter also change.
•
0.01 A units: 2001 to 2042, B001 to B018, 4001 to 4023
•
0.1A units: 2056 to 2082, 4031 to 4060
No signal output available
U4-14
(07D0)
PeakHold Output Freq
Displays the output frequency at which the peak value (rms) of the drive output current is held.
The peak hold current can be monitored by
U4-13 [Peak Hold Current]
.
The peak hold output frequency will be cleared at the next startup and restart of the power supply.
The drive keeps the value that was under hold during baseblock (during stop).
Unit: 0.01 Hz
No signal output available
U4-16
(07D8)
Motor oL1 Level
Shows the integrated value of
oL1 [Motor Overload]
as a percentage of
oL1
detection level.
Unit: 0.1%
10 V: 100%
U4-18
(07DA)
Reference Source
Shows the selected frequency reference source.
The keypad shows the frequency reference source as
“
XY-nn
”
as specified by these rules:
X:
External Reference 1/2 Selection [H1-xx = 2]
selection status
•
1:
b1-01 [Frequency Reference Selection 1]
•
2:
b1-15 [Frequency Reference Selection 2]
Y-nn: Frequency reference source
•
0-01: Keypad (
d1-01 [Reference 1]
)
•
1-00: Analog input (unassigned)
•
1-01: MFAI terminal A1
•
1-02: MFAI terminal A2
•
2-02 to 2-17: Multi-step speed reference (
d1-02 to d1-17 [Reference 2 to 16, Jog Reference]
)
•
3-01: MEMOBUS/Modbus communications
•
4-01: Communication option card
•
5-01: Pulse train input
•
7-01: DriveWorksEZ
•
9-01: Up/Down command
No signal output available
U4-19
(07DB)
Modbus FreqRef (dec)
Shows the frequency reference sent to the drive from the MEMOBUS/Modbus communications
as a decimal.
Unit: 0.01%
10 V = Maximum
frequency (-10 V to +10 V)
U4-20
(07DC)
Option Freq Ref(dec)
Shows the frequency reference sent to the drive from the communication option as a decimal.
10 V = Maximum
frequency (-10 V to +10 V)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...