4.11 Fine Tuning during Test Runs (Adjust the Control Function)
144
YASKAWA
SIEPC71061753A GA500 Technical Manual
◆
Open Loop Vector Control Method
In Open Loop Vector Control, keep
C4-01 [Torque Compensation Gain]
at its default setting (1.00).
If you cannot get speed precision during regeneration in Open Loop Vector Control, set
C3-04 = 1 [Slip
Compensation @ Regen Select = Enabled above 6 Hz]
.
Table 4.18 Parameters for Fine Tuning the Drive (
A1-02 = 2 [OLV]
)
Issue
Parameter Number
Possible Solutions
Default
Recommended Setting
•
Unsatisfactory motor torque
and speed response
•
Hunting or oscillation at mid-
range speeds (10 Hz to 40 Hz)
n2-01 [SpdFeedbackDetectCtr
(AFR) Gain]
•
To increase the speed of torque
or speed response, decrease
the setting value in increments
of 0.05.
•
If hunting or oscillation occur,
decrease the setting value in
increments of 0.05.
1.00
0.50 - 2.00
n2-02
[SpdFeedbackDetCtr(AFR)Time
Const1]
•
To increase the speed of torque
or speed response, decrease
the setting value in increments
of 10 ms and examine the
response.
•
If hunting or oscillation occur
or if the load inertia is too
much, increase the setting
value in increments of 50 ms
and examine the response.
Note:
Make sure that this parameter
setting is:
n2-02 ≤ n2-03
[Automatic Freq Regulator
Time 2]
holds true.
When you adjust
n2-02
, you
must also increase the
C4-02
[Torque Compensation Delay
Time]
value by the same ratio.
50 ms
50 ms to 2000 ms
ov [overvoltage]
occurs when the
drive stops accelerating, starts to
decelerate, or when there are
large changes in the load.
n2-03
[SpdFeedbackDetCtr(AFR)Time
Const2]
•
If
ov
occurs, increase the
setting value in increments of
50 ms and examine the
response.
•
If the response is not
sufficient, decrease the setting
value in increments of 10 ms
and examine the response.
Note:
Make sure that this parameter
setting is:
n2-02 [Automatic
Freq Regulator Time 1] ≤ n2-
03
. When you adjust
n2-03
,
you must also increase the
C4-06 [Motor 2 Torque Comp
Delay Time]
value by the
same ratio.
750 ms
750 ms to 2000 ms
C4-06 [Motor 2 Torque Comp
Delay Time]
•
If
ov
occurs, increase the
setting value in increments of
10 ms and examine the
response.
•
If the response is not
sufficient, decrease the setting
value in increments of 2 ms
and examine the response.
Note:
Make sure that this parameter
setting is:
C4-02 [Torque
Compensation Delay Time] ≤
C4-06
.
When you adjust
C4-06
, you
must also increase the
n2-03
[Automatic Freq Regulator
Time 2]
value by the same
ratio.
150 ms
150 ms to 750 ms
•
Unsatisfactory motor torque
and speed response
•
Hunting or oscillation
C4-02 [Torque Compensation
Delay Time]
•
If torque or speed response are
slow, decrease the setting
value in increments of 2 ms.
•
If hunting or oscillation occur,
increase the setting value in
increments of 10 ms.
Note:
Make sure that this parameter
setting is:
C4-02 ≤ C4-06
[Motor 2 Torque Comp Delay
Time]
.
When you adjust
C4-02
, you
must also increase the
n2-02
[SpdFeedbackDetCtr
(AFR)TimeConst1]
value by
the same ratio.
20 ms
20 ms - 100 ms
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...